Specifications
Chapter6FunctionalParameterDetailVFD‐G7SeriesFrequencyInverterOperationManual
102
Carrier
Frequency↑
Motor temperature rising↓
Output current smoothness↑
Temperature rise of frequency
inverter↑
Leakage current↑
External radiated interface↑
The relation between machine type and carrier frequency is as the following table:
Carrier
Frequency
machine type
Max Carrier
Frequency
(kHz)
Min
Frequency
(kHz)
Default
(kHz)
0.75~11kW
15.0 0.5 4.0
15~55kW
8.0 0.5 3.0
75~400kW
6.0 0.5 2.0
Whenthe outputfrequency of frequency inverter is 0Hz, and it is in vector control or V/F
control and torque lift, there is the voltage output in the frequency inverter, if running in
0Hzinalongtermandthereisvoltageoutput,themotorheatdissipationisbad,itis
easyto
cause the motor heating. The user could set a certain output voltage holding time, after
exceeding this holding time, the output voltage will turn to 0, which could prevent the
motorfromoverheating.
F0.23
Voltage of energy
consumption brake value
Default:130.0%(380V
series)
120.0%( 220V
series)
Setting Range:115.0~
140.0%(Standard
bus-wire voltage)
Thisfunctioncodeisthestartvoltageofsettingenergyconsumptionbrakingunit,ifweset
thisvalueproperly,whichcouldbraketheoverloadeffectively.
F0.24
Given frequency is less than frequency
lower limit
Default:0 Setting Range:0~2
0:Operatingtolowerlimitfrequency