VFDG7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
101
cancelledtoshortenthedecelerationtime.
Decade: Reservation
Hundreds: PWM Selection
0:PWMMode1
ThismodeisthenormalPWMmode,themotornoiseislowinlowfrequencyandthemotor
noiseisbiginhighfrequency.
1:PWMmode2
The noise in this running mode is low, but the wavelength is high, it needs to derate if
selecting
thefrequencyinverterofthisfunction.
Kbit: automatic energy saving
0:Invalid
1:Valid
Theautomaticenergysavingcouldbeobtainedbycheckingtheloadcurrent and adjusting
outputvoltageappropriatelywhenthemotorisintheprocessofnoloadorlightload.This
functionisespeciallyvalidforfanandpumpload.
F0.22
Carrier
frequency
Default:
Machine Type confirmation
Setting scope
0.5150.0kHz
This function adjusts the carrier frequency of the frequency inverter. By adjusting carrier
frequency,themotornoisecouldbelower,thepointofresonanceofthemechanicalsystem
couldbeavoided,whichcoulddecreasethedisturbanceofthecircuittothegroundleakage
current and the disturbance generated by the frequency
inverter. When the carrier
frequencyislower,theoutputcurrentultraharmonicscomponentwillincrease,so theloss
ofmachineandmotortemperaturerising.Whenthecarrierfrequencyishigher,thelossof
machine will lower, the motor temperature rising will lower, but the loss of frequency
inverter will increase, the
temperature rising and disturbance of frequency inverter will
increase. The influence of carrier frequency to the equipment and environment is as the
followingtable:
Motor noise