Chapter6FunctionalParameterDetailVFD‐G7SeriesFrequencyInverterOperationManual
98
button.
F0.14 Control mode Default: 1
Setting:0~2
Selection of the control mode of frequency inverter
0:NoPGSpeedvectorcontrol
No PG vector control mode refers to open‐loop vector control, which is suitable for low
frequencytorque,the applicationwherethespeedcontrolaccuracy requirementishigher,
onefrequencyinvertercanonlydriveonemotor. Suchasmachinetools, centrifuges,draw
bench,injectionmolding
machinesandotherloads.
1:V/Fcontrol
The V/F control is suitable for the applications which accuracy's requirement is not high,
suchasfanandpumploads.
2:NoPGTorquecontrol
Themodeisapplicabletoapplicationswhichtheaccuracy'srequirementoftorquecontrolis
high, such as coiling,
draw bench and other applications. After the drive's operation to
restore the default value, the reference frequency which is set by panel and UP/DOWN
functionterminalswillbeauto‐clear.
☞Note: When selecting the mode of vector’s control, the motor’s nameplate parameter
mustbesetrightlyandthemotorparameter
auto‐learningmustbefinishedbeforerunning
to obtain the accurate motor parameter, Only obtain accurate motor parameter, the high
performance of the vector control could be displayed. By adjusting the vector and torque
control parameter (F3 Group), the vector control performance can obtain better
performance.
F0.15 Model type selection Default: 0
Setting:0~1
0: Applicable to constant torque load
1: Applicable to variable torque load (fan and water pump load)
F0.16 Motor rated voltage Default: 380V
Setting scope:20~2000V