VFD‐G7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
97
Figure 6-4 Illustration of Three-wire Running Mode 1 
Among:SB1:runningbutton(normalopen);SB2:stopbutton(normalclose).
K:forwardandreverseswitch
3: Three-wire control 2 
This three‐wire function terminal mode is enabled terminal, the running command is
generated by SB1 or SB3 and it control the running direction at the same time. The stop
commandisgeneratedbythenormalinputSB2.
Terminal  Setting  Description 
Sx 01 Forward running  
Sy 02 Reverse running  
Sn  03  Three-wire running control 
The control mode is as the following figure6-5. 
Figure6-5 Illustration of Three-wire running mode 2 
Among: SB1: forward running button; SB2: Stop button; SB3: reverse running button. 
4: Three-wire control 3 
The same with three-wire control mode 2, the difference is the stop button is normal open 
0 Forward 
1 Reverse 