Specifications

Chapter6FunctionalParameterDetailVFDG7SeriesFrequencyInverterOperationManual
96
Figure 6-3 Illustration of Two-wire Running Mode 2
Notes: For twowire running mode, when forward function terminal/reverse function
terminalisvalidandthefrequencyinverterstopsduetothestopcommandcausedbyother
source,evenifthecontrolterminalforwardfunctionterminal/reversefunctionterminalstill
Reservevalid,thefrequencyinverterwon’trunafterthedisappearanceofstop
command,if
the user want the frequency inverter to run, it need to trigger the forward function
terminal/reversefunctionterminalagain.
2: Three-wire control 1
This threewire function terminal mode is enabled terminal, the running command is
generated by forward function terminal, the direction command is generated by reverse
functionterminal,thethreewirefunctionterminalisnormalclose.
Terminal Setting Description
Sx 01 Forward running
Sy 02 Reverse running
Sn 03 Three-wire running control
The control mode is as the figure 6-4.
0 1 Stop
1 0 Forward
1 1 Reverse
K Running
direction
Sx Forward running
Sy Reverse running
COM
K1
K2