Installation Instructions
SSB 6720818454 (2016/02) US
Installation | 27
Pipe diameter per boiler
Material Item Standard [USA]
Standard
[Canada]
SSB
255
SSB
399
SSB
512
PVC schedule 40,
80
1
Flue gas or
combustion air
ANSI/ASTM D1785
BH Gas venting
systems,
ULC S636
2
,
Class IIA - PVC,
Class IIB - CPVC,
Class IIC -
Polypropylene
3” (80mm)
4” (100mm)
3” (80mm)
4” (100mm)
4” (100mm)
PVC-DWV
Flue gas or
combustion air
ANSI/ASTM D2665
3” (80mm)
4” (100mm)
4” (100mm) 4” (100mm)
CPVC schedule
40, 80
Flue gas or
combustion air
ANSI/ASTM F441
3” (80mm)
4” (100mm)
4” (100mm) 4” (100mm)
PP
Flue gas or
combustion air
ANSI Cat IV
Approved
Polypropylene
3” (80mm)
4” (100mm)
4” (100mm)
5” (130mm)
4” (100mm)
5” (130mm)
PP-Flex
Flue gas or
combustion air
ANSI Cat IV
Approved
Polypropylene
3” (80mm)
4” (100mm)
4” (100mm)
5” (130mm)
4” (100mm)
5” (130mm)
Stainless Steel
AL29-4C
Flue gas or
combustion air
UL1738
3” (80mm)
4” (100mm)
4” (100mm)
5” (130mm)
4” (100mm)
5” (130mm)
PVC
Pipe cement/
primer
ANSI/ASTM D2564 X X X
CPVC
Pipe cement/
primer
ANSI/ASTM F493 X X X
Tab. 4 Approved Flue gas or combustion air materials and ttings per boiler
1 PVC must not be used for vent material when a glycol mixture is used in the boiler circuit.
2 Components of the certied vent systems must not be interchanged with other vent systems or unlisted pipe ttings. Plastic components, and specied
primers and glues of the certied vent system must be from a single system manufacturer and not intermixed with other system manufacturer’s vent
system parts. For installations in Canada, eld supplied plastic vent piping must comply with CAN/CSA B149.1 (latest edition) and be certied to the
Standard for Type BH Gas Venting systems. ULC S636.
The supplied vent connector and separate available vent terminations are certied as a part of the boiler.
Standard straight pipes, 90°-elbows or Tees are approved as roof or wall terminations in all the approved materials. Furthermore the following terminations
are approved. For details please refer to the supplier’s information.
Roof Terminal Material Supplier Part Number
3” (125 mm)
4” (100mm)
Concentric kits
PVC or CPVC
IPEX System 636
Type IIa & IIb
196006 (PVC), 197009 (CPVC)
196021 (PVC), 197021 (CPVC)
3” / 5” (80/125 mm)
concentric
PP
M&G Duravent PolyPro
or
Centrotherm InnoFlue
3PPS-VKL (M&G Duravent)
or
ICRT3539 (Centrotherm)
4”/6” (100/150 mm)
Concentric
PP
M&G Duravent PolyPro
or
Centrotherm InnoFlue
4PPK-VKL (M&G Duravent)
or
ICRT 4679 (Centrotherm)
3” (80 mm)
Chimney Cap
PP Flex
M&G Duravent PolyPro
or
Centrotherm InnoFlue
3PPS-FKL (M&G Duravent)
or
ISCP03 (Centrotherm)
4” (100 mm)
Chimney Cap
PP Flex
M&G Duravent - PolyPro
Centrotherm - Innoue
SW Flex
4PPS-FKL (M&G Duravent)
or
ISCP04 (Centrotherm)
5” (130 mm)
6” (150 mm)
8” (200 mm)
Vertical termination for commercial
systems
PP M&G Duravent - PolyPro
5PPS-VTM
6PPS-VTM
8PPS-VTM