Installation Instructions
Inspection and maintenance | 33
6 720 805 218 (2016/02)SB625WS/SB745WS
8.2.2 Adjusting the door
Make sure that the door presses uniformly all around the double seal to
prevent dangerous fumes escaping into the air. Proceed as follows to
adjust the door seals.
System A
▶ Fit the door and tighten the main fixing bolts [2] until the seals start
to compress.
▶ Loosen the safety bolts [1] then fully screw in the main door fixing
bolts [2].
▶ Tighten the safety bolts [1].
Fig. 33 Adjust the door
[1] Safety bolts
[2] Fixing bolts
System B (larger size)
▶ Put the door in its correct position.
▶ Tighten the main locking screws [1] until the packing starts to be
compressed.
Fig. 34 Position the door
8.3 Cleaning the boiler
Use a cloth damped in soapy water to clean the boiler’s external
paneling.
To remove stubborn marks, use a cloth damped in a 50% mix of water
and denatured alcohol or a suitable cleaning product.
Carefully dry the boiler after cleaning.
Clean the boiler and remove any carbon deposits from the surfaces of
the heat exchanger at least once a year. This not only extends the
boiler’s working life, but also keeps it efficient in terms of heat output
and consumption.
2
1
6 720 805 218-40.1T
Make sure that the door is properly adjusted after every
maintenance operation.
DANGER: Risk to life from electric shock!
▶ Before opening a unit: disconnect electrical power
and lock to prevent accidental reactivation.
WARNING: System damage!
▶ Do not use abrasive cleaning pads or powder
detergents.
NOTICE:
The combustion chamber and flues must be cleaned
periodically - at least once a year - by a qualified
technician.
1
1
6 720 805 218-41.1T