Installation Instructions

13
System inspection and maintenance
Logano G315 – 6 720 817 939 (2016/04)34
Take the flue gas baffle plates forwards out of the flue gas passages
(Fig. 61, [1 – 4]).
Fig. 61 Flue gas baffles, removing
The various brush types available from Buderus (optional extras) are
shown in Fig. 62.
Fig. 62 Cleaning brushes
Clean the flue gas passages (Fig. 63, [1]) starting at the front and
working towards the back with cleaning brushes 1 and 2 (Fig. 62).
Clean the rear wall of the combustion chamber with cleaning brush 3.
Clean the rest of the combustion chamber (Fig. 63, [2]) with
cleaning brush 2.
Clean the bottom flue gas passages from the front with cleaning
brush 2 (Fig. 63, [1]).
Fig. 63 Heat exchanger heater flue, cleaning
Undo the four self-tapping screws on the rear boiler panel at the
bottom.
Remove bottom rear boiler panel.
Loosen spring hooks below the flue outlet ( Fig. 35, page 22).
Fold both ends of the thermal insulation up (Fig. 64, [1]) and fasten
in this position with the spring hooks.
Remove the cleanout covers from the rear section (Fig. 64, [2]) and
on the draft diverter (Fig. 64, [3]).
Remove all loose combustion residues from the combustion
chamber, the flue gas passages and the draft diverter.
Check sealant ropes on the openings of the cleanout covers and
burner door. Replace damaged or hardened sealant ropes.
Fig. 64 Removing the cleanout cover
Clean flue gas baffle plates with the cleaning brushes.
You can obtain sealant ropes from your nearest branch
office.