Installation Instructions

9
Installing a control panel
Logano G315 – 6 720 817 939 (2016/04) 29
9.5 Wiring Hydrolevel Hydrostat with Beckett CF500 &
CF800 Burner
In applications requiring CSD-1 compliance a manual safety high limit
switch must be installed wired from L1 to terminal LMT Interrupting
power to the burner
Fig. 56 Wiring Hydrolevel with Beckett CF500/CF800 (for 120V burners only)
[1] Hydrolevel Hydrostat
[2] Becket CF500/CF800
L1 Line 1 power (hot)
L2 Line 2 power (neutral)
LMT Limit control terminal
MTR Motor control terminal
S1 Oil valve
S2 Oil valve (on cleancut pump)
TRANS Ignition transformer
VLV Valve control terminal
——— Factory Wiring
------ Wiring supplied by installer
L1 L2 C1 C2 B1 B2 I1 I2
Z
T
TV
L
B1 - L
B2 - N
N
120VAC
G
EQUIP
GND
TERMINAL
+
1 2
LIMITS
DETECTOR
A
K
D
A
A
C
F
LINE VOLTAGE SERVICE 120V 60Hz
FROM FUSED DISCONNECT SWITCH
SUPPLIED BY INSTALLER
OPERATOR
A
TRANS
S1
MOTOR
7505P
S2
AD
LMT
L1
L1
IGN
TR
TW
VLV
CAD
CAD
MTR
L2
L2
B
B
6 720 817 939-10.1T