Installing a control panel
Logano G315 – 6 720 817 939 (2016/04) 27
9.4 Wiring Hydrolevel Hydrostat with Riello F15 Burner
For ease of installation, leave the control box off the sub-base while
completing the electrical connections to the burner.
Fig. 53
[1] Hot conductor terminal (BLACK WIRE)
[2] Ground conductor terminal (GREEN WIRE)
[3] Strain relief clamp
[4] Wire access hole (Use BX electrical connector)
[5] Neutral conductor terminal (WHITE WIRE)
Ground wire from power supply to G screw on Hydrolevel and ground
terminal on burner (Fig. 53).
The SAFETY SWITCH in the 530SE CONTROL BOX is equipped with a
contact allowing remote sensing of burner lockout. The electrical
connection is made at terminal 4 on the SUB-BASE. Should lockout
occur the 530SE CONTROL BOX will supply a power source of 120VAC
to the suggested connected terminal. The maximum allowable current
draw on this terminal (4) is 1 Amp.
In applications requiring CSD-1 compliance a manual safety high limit
switch must be installed Interrupting power to the burner.
Fig. 54 Installation of a high limit switch
CAUTION: Risk of system damage from incorrect
connections.
Wrong connections can cause damage to the primary
safety control.
Connect the hot (black) wire to the L terminal and
the neutral (white) wire to the N terminal.
Do not connect either wire to the terminal.
NOTICE: Risk of system damage from improper oil line
connections.
Improper oil line connections can lead to failures of the
pump shaft seal.
Do not activate the burner until proper oil line
connections have been made.
NOTICE: Risk of system damage from incorrect
connections.
If a neutral or ground lead is attached to terminal 4, the
control box on the burner will be damaged should
lockout occur.
Do not attach a neutral or ground wire to terminal 4.
1
2
3
4
5
6 720 817 939-09.1T
EARTH GROUND (GREEN)
NEUTRAL (WHITE)
HOT LINE (BLACK)
N
L
120V
AC
LINE SAFETY
SWITCH
OPERATING
LIMIT SWITCH
SAFETY
LIMIT SWITCH
FUSE 15A
6 720 817 939-08.1T