Installation Instructions

8
Connecting the boiler on the flue gas side
Logano G315 – 6 720 817 939 (2016/04)24
Attach the front panel (Fig. 43, [3]) at the bottom in the center to the
base panel (Fig. 43, [2]).
Attach the front panel at the top to the folded edge of the front cover
(Fig. 43, [1]).
Fig. 43 Fitting the front panel
Hook burner door panel into the cut-outs in the front cover (Fig. 44,
[3]).
Fig. 44 Attaching the burner door panel
8 Connecting the boiler on the flue gas side
This chapter explains how to connect the boiler on the flue gas side.
8.1 Installing a vent pipe sealing collar (accessory)
Push the vent pipe as far as possible onto the draft diverter outlet.
Place the vent pipe sealing collar around the vent pipe and draft
diverter outlet so that it overlaps at the top.
Place hose clamps (Fig. 45, [4]) over the vent pipe sealing collar.
One of the hose clamps must press onto the draft diverter outlet and
and one onto the vent pipe.
Tighten hose clamps.
The vent pipe sealing collar must fit smoothly and firmly in place after
tightening the hose clamps.
Fig. 45 Installing the vent pipe
[1] Vent pipe sealing collar
[2] Flue gas temperature sensor
[3] Sleeve
[4] Vent pipe
[5] hose clamps
[6] Exhaust Manifold
[A] 2 × Vent pipe diameter, at least 28 22/64 inches (720 mm)
8.1.1 Installing a flue gas temperature sensor (accessory)
Weld a sleeve (Fig. 45, [3]) at a distance of two (2) × vent pipe
diameters (A) – min. 720 mm – from the draft diverter in the vent
pipe.
Fit the flue gas temperature sensor (Fig. 45, [2]) as described in the
separate installation manual.
3
2
1
6 720 817 939-05.1T
1
6 720 817 939-06.1T
We recommend you use a vent pipe sealing collar
( Fig. 45, [1]).
Retighten the hose clamps if required.