Installation Instructions

7
Boiler block assembly
Logano G315 – 6 720 817 939 (2016/04)18
7.6.2 Sealing leaks
If a hub connection is leaking, first drain the water through the fill/
drain valves.
Remove supply pipe.
Undo nuts on four tie rods and remove tie rods.
Separate the boiler at the leak location by driving (ponding) in flat
wedges or chisels between the sections at the designated points
(Fig. 24, [1 and 2]) at the top and bottom.
Fig. 24 Separating the boiler block
7.6.3 Supply flange with safety components, return flange
Fig. 25 Return flange
[1] Boiler connection
[2] System connection
Use new nipples and new sealant rope for the
reassembly.
Pull the boiler back together and repeat the leak test.
6 720 817 939-12.1T
1
2