z Screw studs included with the B-Kit to the burner
door.
z Fit the burner to the hole circle of the burner door.
z Install burner with the correct nozzle and settings
(air, pump pressure, turbulator settings, flange
position).
z Place the seal on the studs and secure the burner
with the included nuts.
z Follow the manufacturer's direction for installation,
fine adjustment and regular maintenance
procedures.
z Wire up the burner (see Î documentation for
burner).
8.5 Providing a fuel supply
Make the fuel connection in accordance with all locally
applicable regulations. We recommend the installation
of a fuel filter.
z Visually inspect the fuel pipe and clean or replace, if
necessary.
z Install a shut-off valve into the fuel supply pipe.
z Connect the fuel pipe free of stress to the boiler.
z Check the fuel line for leaks.
8.6 AquaSmart
TM
installation
The AquaSmart
TM
controls the boiler supply
temperature.
z For Installation and Operation of the AquaSmart
TM
Control and sensor well see the AquaSmart
TM
Installation Instructions supplied with the control. For
wiring diagrams of the AquaSmart
TM
Î Chapter 12,
page 57.
z Install AquaSmart
TM
and sensor well as specified by
the installation manual.
For operating the boiler with AquaSmart
TM
control see
instructions supplied with the controller.
Fig. 51 Burner door mounting holes
4 3/8"
5 7/8"
NOTICE
Approved burners with accessories (such
as aquastat and circulator) are also
available as a package from Buderus
Hydronic Systems.
NOTICE
For the correct burner settings see the
Î documentation for the flue system and
the Î burner.