Specifications

Logamax plus GB142 applications manual | 01.2012 Technical speci cations are subject to change without prior notice
GB142 Applications Manual
| 17
2.4.6 Mixing Module MM10 Wiring Diagram
120
14AWG
L
120 V 60Hz
120 V 60Hz
14AWG,
Max. 5A
14AWG,
Max. 5A
18AWG
18AWG
18AWG
Main power
supply
run time:
Valve actuator
motor
System
-
+
-
+
2)
1) Requires 120V mixing valve with 3-point floating actuator.
Maximum current: 5A
2) Hot: increase hot water delivery to zone
Cold: decrease hot water delivery to zone
Fuse
5 AT
Notes:
Polarity matters on EMS/RC bus: Connect 1 to 1 and 2 to 2.
Implement the installation, fuse protection, main isolator,
emergency stop switches and safety measures in accordance with
local/national regulations.
Warning! Ground yel/grn must not be used as a control line.
Ensure phases are connected correctly.