Installation and Service Instructions Logamatic 4323 Control Panel For heating contractors 6 720 618 588 - 11/2008 US/CA Read carefully prior to commissioning and service work
Contents 1 Safety . 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 About this manual . . . . . . . . . . . . . . . Intended use . . . . . . . . . . . . . . . . . . Standards, regulations and directives . . . Key to symbols . . . . . . . . . . . . . . . . . Please observe these notes . . . . . . . . . Important instructions for commissioning . Cleaning the control panel . . . . . . . . . . Disposal . . . . . . .
Contents 11.3 11.4 11.5 11.6 11.7 11.8 11.9 11.10 11.11 11.12 11.13 11.14 11.15 11.16 11.17 11.18 11.19 11.20 11.21 11.22 11.23 11.24 11.25 Adjusting base point temperature . . . . . . . . . Setting design temperature . . . . . . . . . . . . . Minimum supply temperature . . . . . . . . . . . . Maximum supply temperature . . . . . . . . . . . Selecting remote control . . . . . . . . . . . . . . . Maximum room effect . . . . . . . . . . . . . . . . Selecting setback type . . . . . . . . . . . . . . . .
Contents 13 Substations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 13.1 Setting the minimum warm up temperature . . . . . . . . . . . . . . . . . . . . . . . . . 92 13.2 Setting the maximum warm up time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 13.3 Setting boiler raising . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 14 Characteristic heating curve 15 Running relay test . . . . . . . . . . .
Safety 1 Safety 1.1 About this manual This manual contains important information regarding the safe and appropriate commissioning and servicing of the Logamatic 4323 control panel. This manual is intended for heating contractors who, due to their training and experience, are knowledgeable in handling heating systems and domestic hot water installations. Only carry out service measures yourself if you have this technical expertise. 1.
1 Safety CAUTION! RISK OF INJURY/ SYSTEM DAMAGE 1.6 due to operator error! z Before switching the control panel on, check that its manual switches and those on the function modules are set to "AUT". Operator errors can cause injury and damage to property. z Make sure that children never operate the appliance unsupervised or play with it. z Make sure that only personnel trained to operate the appliance correctly have access to it.
Product description and scope of delivery 2 Product description and scope of delivery 2.1 Product description 2 The digital Logamatic 4323 control panel can be used as a stand-alone heating zone controller managing the heat generated by a manually or indirectly-fired buffer tank, or as a substation, for the demand-dependent control of a supply pump. The heating zone control function is part of the standard equipment level (one heating zone with actuator).
Setting parameters and display data 3 3 Setting parameters and display data Some options are only displayed subject to the modules that have been installed and the adjustments made earlier.
Controls and MEC2 remote control 4 Controls and MEC2 remote control 4.1 Control panel controls Fig. 2 Control panel interface (standard delivery) 1 On/Off switch 2 Connector for external service equipment 3 L1, L2 fuses Fig. 3 4 Modules installed 1 Slot 1: e.g. FM442 – heating zone 1, heating zone 2 2 Slot 2: e.g. FM442 – heating zone 3, heating zone 4 A Slot A: ZM433 – supply for external heat sources, heating zone 0 B Slot B: MEC2 (CM431) – MEC2 remote control 3 Slot 3: e.g.
Controls and MEC2 remote control 4 4.2 MEC2 remote control Fig.
Modules and their functions 5 5 Modules and their functions All modules are shown here that are or can be installed in your Logamatic 4323 control panel.
Modules and their functions 5 5.1 CM431 controller module Setting the control panel address Address settings (Æ Fig. 5, [1]) for the Logamatic 4323 control panel are made on the CM431 module (behind the MEC2 remote control). z Remove the MEC2 remote control. z You can now set the control panel address with a screwdriver (Æ Fig. 5). 1 Fig. 5 Address 0 Description Stand-alone control panel: Set the address to 0 if the control panel operates as stand-alone equipment (factory setting).
Modules and their functions 5.2 5 NM482 power module Terminator when networking several control panels RISK OF FATAL INJURY due to electric shock! WARNING! 1 z Make sure that all electrical work is carried out by a trained contractor. z Before opening the control panel: isolate all poles of the power supply and secure against accidental reconnection. 2 To ensure fault-free data transmission between several control panels, install a terminator for the two control panels which are furthest apart.
5 5.3 Modules and their functions ZM433 central module The ZM433 module controls to transfer heat, in case of demand, from the external heat sources to the heating system. This module also controls one heating zone with mixing valve. The manual switches on the module only have service and maintenance functions and only affect 120 V outputs. If the manual switches are not set to automatic, a corresponding message appears on the MEC2 remote control, and the fault indicator lights up.
Modules and their functions 5 Supply function Manual switch supply pump (Æ Fig. 8, [1]) USER NOTE In normal mode, the manual switch should be set to "AUT". The 0 and 3 (manual mode) positions are special settings that should only be made by heating contractors. 3 : The supply pump is switched on. AUT: The supply pump operates automatically. 0: The supply pump is switched off. The control functions continue to operate. 2 1 Fig.
5 Modules and their functions U terminals 1 – 4 External set values can be received or issued via the U terminals of the ZM433 central module. 1 2 3 4 U 1 2 1 2 1 2 3 1 2 1 2 1 2 3 4 WF BF FV FZB FA U USER NOTE To avoid generating undefined input values, never apply voltages greater than 10 V to the 0 – 10 V input. 2 1 J1 Fig.
Modules and their functions 5 U terminals 3 (-) and 4 (+), 0 – 10 V output Via terminals U 3 and U 4 on the ZM433 central module, a 0 – 10 V signal can be supplied externally to provide a set value. This would be the maximum system supply temperature for all connected heating zones. Jumper plug J 1 The set point can also be output as a 0 – 20 mA signal. The jumper J 1 should then be repositioned from to . Fig.
5 5.4 Modules and their functions FM441 function module (accessory) The FM441 module controls one heating zone and one DHW heating consumer. The manual switches on the module only have service and maintenance functions and only affect 120 V outputs. Only install this module in the control panel once. If the manual switches are not set to automatic, a corresponding message appears on the MEC2 remote control and the fault indicator lights up.
Modules and their functions 5 Heating zone and DHW function Manual heating zone switch (Æ Fig. 13, [1]) and DHW (Æ Fig. 13, [2]). for heating zone: for DHW supply: USER NOTE In normal mode, the manual switch should be set to "AUT". 2 The positions 0 and 3 (manual mode) are special settings reserved for heating contractors only. 3 : The heating pump or tank primary pump is switched on. The mixing valve is switched to zero volt and can be manually operated. The DHW recirculation pump is switched off.
5 5.5 Modules and their functions FM442 function module (accessory) The FM442 module controls two independent heating zones with mixer. Several of these modules can be used in one control panel. The manual switches on the module only have service and maintenance functions and only affect 120 V outputs. If the manual switches are not set to automatic, a corresponding message appears on the MEC2 remote control, and the fault indicator lights up.
Commissioning the MEC2 remote control 6 6 Commissioning the MEC2 remote control You can use the MEC2 remote control for all Logamatic 4000 control panels. The MEC2 remote control can: – be installed directly in the control panel or – be used as a remote control unit in a wall retainer or – connected to an adapter with a separate power source. The MEC2 starts initialization after a power supply has been connected. MEC is initializing The display shows "MEC is initializing".
6 Commissioning the MEC2 remote control MEC2 with set parameters installed in control panel After the MEC2 has been installed in the control panel, the two adjacent displays will initially be shown again. MEC is initializing connection with control module address established XX a) Alternative controller model other controller model Initially, only data from the control panel can be downloaded, if the type of control panel varies from that entered in the MEC2 remote control.
Commissioning the MEC2 remote control 6 Press "AUT" = "data writing to control panel". The display will then show the adjacent message. data writing to control panel Press "Night mode" = "data reading from control panel". The display will then show the adjacent message.
7 7 Calling up the service level Calling up the service level Access to the service level is password protected. The service level is intended for contractors only. Unauthorized access to the service level invalidates your warranty! The controls marked in gray are used for this function. + + Press "Display" + "Heating zone" + "Temp" simultaneously and then release. The service level is now enabled.
Calling up the service level 7 Calling up submenus Select the main menu (see above) whose submenu you want to call up. Press "Display". You can access all submenus of the main menu selected by turning the dial. Example main menu: general data – min outdoor temp – building type – ... – min outdoor temp + Press and hold down "Display". You can modify the adjustable parameters of the submenu selected by turning the dial. For example, you might select functions or temperatures.
8 8 Calling up and modifying settings Calling up and modifying settings USER NOTE The menus displayed on the MEC2 remote control of the control panel depend on which modules are installed and on their settings. These service instructions only describe the menus of the ZM433 central module (standard equipment) and those of the most commonly used function modules FM441 and FM442 (accessories). All other menus are explained in the separate technical documentation of each respective module.
General data 9 9 General data USER NOTE In main menu "general data" you can adjust values for the submenus listed relating to the heating system and the characteristics of the house in question. The following pages explain how to adjust values relating to the submenus. + + Call up the service level. "general data" appears as the first main menu. Press "Display" to call up a submenu (here: "min outdoor temp"). The display shows the selected submenu.
9 9.1 General data Minimum outdoor temperature The minimum outdoor temperature is a statistically-calculated average value of the coldest outdoor temperatures over the past few years. It influences the gradient of the heating curve (colder: shallower heating curve; hotter: steeper heating curve). + + Fig.
General data 9.2 9 Building type Input the insulation capacity of the building in building type. Different types of construction have different heat storage capacities. This function sets the heating system to the specified construction type. The heat storage capacity is divided into three classes: + + light = low heat storage capacity, e.g. prefabricated building, woodframe construction, medium = average heat storage capacity, e.g.
9 9.3 General data Summer/winter time changeover z To adjust for daylight savings time, open the flap of the MEC2 for the keypad of the second control level. Hold down "Time" and select the desired time with the dial. + 30 In spring, set the time one hour ahead (dial clockwise); in fall, set the time one hour back (dial counterclockwise). Logamatic 4323 - Technical specifications are subject to change without prior notice.
General data 9.4 9 Remote control The remote control offers the option of external data input or modification via service tools (optional). + yes = remote control not available no = remote control is not available, but system data can be downloaded and monitored. Call up the service level. "general data" appears as the first main menu. + Press "Display" to call up a submenu (here: "min outdoor temp"). The display shows the selected submenu.
9 9.5 General data Manual switch fault message A fault message can be displayed on the MEC2 if a manual switch on a function module is set to 3. + Call up the service level. "general data" appears as the first main menu. + Press "Display" to call up a submenu (here: "min outdoor temp"). The display shows the selected submenu. general specs min outdoor temp 14°F Turn the dial until submenu "fault manual switch" appears. The display shows the selected submenu.
General data 9.6 9 Automatic service call You can generate an automatic service call at the operator level on the MEC2 remote control display. You can set the following: – service call after date. Enter the date of the next scheduled service (01/01/2000 – 12/31/2088). – Maintenance according to "hours run" (only for control panels with direct boiler control). USER NOTE The service call after "hours run" time is not possible with this control panel. + Call up the service level.
9 General data + Hold down "Display" and turn the dial until the desired value appears (here: "10/01/2008"). The display shows the set value. Release "Display" to save your input. general specs service call on 10/01/2008 Press "Back" to return to the next level up. USER NOTE The service call is recorded in the fault log and can be transferred via the Logamatic telecontrol system. The status of the service call can be checked in the "act system data" menu.
General data 9.7 9 0 – 10 V input As soon as a module with 0 – 10 V input has been installed in the control panel, the following screens appear as listed in the table below: Module Name Temperature control Power control FM448 fault module X FM456 KSE 2 (EMS) X X (CM431 V6.xx or higher) FM457 KSE 4 (EMS) X X (CM431 V6.xx or higher) FM458 Strategy module X X (CM431 V8.xx or higher) ZM433 Sub station X USER NOTE This manual only describes temperature control.
9 9.8 General data Temperature control 0 – 10 V input If you have selected "temperature" for the 0 – 10 V input, you can adapt the start and stop point, if required, for the external 0 – 10 V input. You can set the following: – The set point in °F (°C) for 0 V ("temperature 0V corresp. to") – The set point in °F (°C) for 10 V ("temperature 10V corresp. to") The following linear curve is calculated from these values: Fig.
General data 9 Turn the dial until submenu "temperature 10V corresp. to" appears. + Hold down "Display" and turn the dial until the desired set value appears (here: "194°F" (90°C)). The display shows the set value. general specs temperature 10V corresp. to 194°F Release "Display" to save your input.
10 Module selection 10 Module selection On starting the Logamatic 4323 control panel or after a system reset, the modules are automatically recognized and their information downloaded. Example: Slot 1: FM442 Slot 2, 3 and 4: N/A However, these modules can also be set manually if necessary. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "module selection" appears. The display shows the selected main menu.
Heating zone data 11 11 Heating zone data The following heating systems can be selected: – "none" The heating zone function is not required. All following submenu items for "heatingzone data" are not applicable. – "radiator" or "baseboard" The heating curve is automatically calculated for radiators or convectors, depending on the required curve. – "floor" A flatter heating curve is automatically calculated for lower design temperatures.
11 Heating zone data 11.1 Heating system selection Example: You want to set "floor" for submenu "heating system" in main menu "heating zone 2". + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "heating zone + no." appears (here: "heating zone 2"). The display shows the selected main menu. service level heating zone 2 Press "Display" to call up a submenu (here: "heating system"). The display shows the selected submenu.
Heating zone data 11 11.2 Renaming heating zone Instead of the description "heating zone + no.", you can select a different designation from the default list. + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "heating zone + no." appears (here: "heating zone 2") Press "Display" to call up a submenu (here: "heating system"). The display shows the selected submenu.
11 Heating zone data 11.3 Adjusting base point temperature This function will only be displayed for "low level" heating systems. By setting the "heating system low level" you have determined a straight heating curve using the base point and design temperatures. With the base point temperature, you determine the start of the heating curve. The base point temperature is applicable for an outdoor temperature of 68 °F (20 °C). + + Call up the service level. "general data" appears as the first main menu.
Heating zone data 11 11.4 Setting design temperature The design temperature is the supply temperature at the adjusted minimum outdoor temperature (Æ Chapter 9.1). The following applies to "low level" heating systems: – Set the design temperature at least 18 °F (10 °C) higher than the base point temperature. – Changing the design temperature allows the heating system to operate with a flatter or steeper heating curve. This function will not be displayed with "room thermostat" heating systems.
11 Heating zone data 11.5 Minimum supply temperature The minimum supply temperature limits the heating curve to a minimum set point. This function will not be displayed with "constant" heating systems. Change value only if necessary. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "heating zone + no." appears (here: "heating zone 2"). Press "Display" to call up a submenu (here: "heating system"). The display shows the selected submenu.
Heating zone data 11 11.6 Maximum supply temperature The maximum supply temperature limits the heating curve to a maximum set value. This function will not be displayed with "constant" heating systems. Change value only if necessary. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "heating zone + no." appears (here: "heating zone 2"). Press "Display" to call up a submenu (here: "heating system"). The display shows the selected submenu.
11 Heating zone data 11.7 Selecting remote control Under this menu item you can specify whether a remote control for the heating zone is installed. You can select: – No remote control – Remote control with display (MEC2) "MEC heatingzones" If "remote control w/ display" is selected for several heating zones, these are grouped as "MEC heatingzones".
Heating zone data + 11 Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "heating zone + no." appears (here: "heating zone 2"). Press "Display" to call up a submenu (here: "heating system"). The display shows the selected submenu. heatingzone data 2 heating system radiator Turn the dial until submenu "remote control" appears. The display shows the selected submenu.
11 Heating zone data 11.8 Maximum room effect This function will only appear if a remote control has been selected, but will not be shown for "room thermostat" heating systems. The maximum room effect limits the effect of the actual room temperature (room temperature hook-up) to the set supply temperature. This value determines the maximum possible room temperature setback in those rooms that are supplied via the currently selected heating zone and where there are no remote control units installed.
Heating zone data 11 11.9 Selecting setback type The following functions for reduced mode or night mode can be selected: – "outdoor setback" determines the outdoor temperature limit. The heating zone is switched off when this value is exceeded. Below this limit, the heating system heats to the set night temperature. – With "room setback" you determine a night temperature as the room temperature. The heating zone is switched off when this value is exceeded.
11 Heating zone data Turn the dial until submenu "type of setback" appears. The display shows the selected submenu. heatingzone data 2 type of setback outdoor setback + Hold down "Display" and turn the dial until the desired value appears (here: "shut down"). The display shows the set value. heatingzone data 2 Release "Display" to save your input. type of setback shut down Press "Back" to return to the next level up.
Heating zone data 11 11.10Setting outdoor setback temperature Enter the outdoor temperature at which the heating operation should change over from "shut down" to "setback" if you have selected "outdoor setback" as setback type. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "heating zone + no." appears (here: "heating zone 2"). Press "Display" to call up a submenu (here: "heating system"). The display shows the selected submenu.
11 Heating zone data 11.11Vacation setback type A separate setback type can be set for the time of the vacation. For explanations of possible settings, see Chapter 11.9. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "heating zone + no." appears (here: "heating zone 2"). Press "Display" to call up a submenu (here: "heating system"). The display shows the selected submenu.
Heating zone data 11 11.12Stopping setback at low outdoor temperatures This feature allows interruption of setback when the actual temperature falls below a selected adjusted outdoor temperature, to prevent the living space cooling down excessively. USER NOTE Setback will not be blocked in manual mode or in vacation mode. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "heating zone + no." appears (here: "heating zone 2").
11 Heating zone data 11.13Setting supply setback Because no remote control can be connected to the "constant" heating system, a setback entry for the "setback" and "outdoor setback" setback types can be made in this submenu item. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "heating zone + no." appears (here: "heating zone 2"). Press "Display" to call up a submenu (here: "heating system"). The display shows the selected submenu.
Heating zone data 11 11.14Room temperature offset This setting is only recommended if no remote control has been installed inside the living space. If the average actual temperature measured with a thermometer deviates from the set temperature for some time, this function enables a matching of both values.The calibration moves the heating characteristic curve at the same time. The changes take effect after a time delay.
11 Heating zone data 11.15Automatic adaptation This function will only appear if "radiator", "baseboard" or "floor" has been selected as the heating system. The "auto adaptation" is not activated at the factory. Where a remote control with room temperature sensor is installed in the room, the heating curve is automatically adjusted to the building by monitoring the room and supply temperature.
Heating zone data 11 11.16Setting switch optimization The function "optimization for" is not enabled at the factory. Install a remote control with room temperature sensor to enable the "optimization" function. The following variations are possible: – Heat-up starts before the actual switching time if "start-up" has been selected. The control panel calculates the start time so that the set room temperature is achieved at the set start point.
11 Heating zone data The display shows the selected submenu. heatingzone data 2 heating system radiator Turn the dial until submenu "optimization for" appears. The display shows the selected submenu. heatingzone data 2 optimization for none + Hold down "Display" and turn the dial until the desired value appears (here: "shut down"). The display shows the set value. heatingzone data 2 optimization for shut down Release "Display" to save your input. Press "Back" to return to the next level up.
Heating zone data 11 11.17Setting switch-off optimization time If you have selected "shut down" or "startup/shutdown" in section 11.16, you can enter from when setback mode should begin. Change the setting only if necessary. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "heating zone + no." appears (here: "heating zone 2"). Press "Display" to call up a submenu (here: "heating system"). The display shows the selected submenu.
11 Heating zone data 11.18Setting frost protection temperature The frost protection temperature only needs to be changed in special cases. The circulation pump is automatically switched on as soon as the preset outdoor temperature threshold is reached. + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "heating zone + no." appears (here: "heating zone 2"). Press "Display" to call up a submenu (here: "heating system").
Heating zone data 11 11.19Setting DHW priority The circulation pumps of all heating zones are switched off while DHW is being heated if you activate the function "DHW priority". In mixed heating zones, the mixer is moved towards "Mixer closes" (colder). + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "heating zone + no." appears (here: "heating zone 2"). Press "Display" to call up a submenu (here: "heating system").
11 Heating zone data 11.20Input heating zone actuator You may determine via the "actuator" function, whether or not the system is equipped with a heating zone actuator (mixer). The control panel drives the actuator if it is installed in the heating zone (mixer). The heating zone is controlled via the boiler supply temperature if no heating zone actuator is installed. + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "heating zone + no.
Heating zone data 11 11.21Entering actuator run time Here you can enter the actuator run time of existing actuators. Generally, actuators have a run time of 120 sec. USER NOTE If you notice a constant oscillation of the mixer, you can slow down the control characteristics by reducing the actuator run time. Then the constant cycling of the mixer will stop. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "heating zone + no.
11 Heating zone data 11.22Boiler temperature increase If a heating zone is controlled with an actuator, a higher set value should be set for the boiler than the normal set value for the heating zone. The value "boiler temp rise" corresponds to the temperature differential between the set boiler temperature and the set heating zone temperature. + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "heating zone + no.
Heating zone data 11 11.23External changeover Using the "external changeover" function, you can use an on-site switch at terminals WF1/2/3 (pink) to change the operating mode of a heating zone. This is where you configure this control panel input. The menu item "external changeover" will only be displayed if "none" was selected under parameter "remote control". The menu item is also not shown if the "room thermostat" heating system is selected, because this requires a remote control.
11 Heating zone data + Hold down "Display" and select the desired value with the dial (here: "via WF1/2/3"). The display shows the set value. heatingzone data 2 external day/night/auto via WF1/2/3 Release "Display" to save your input. Press "Back" to return to the next level up. external day/night/auto 66 Input range Factory setting none via WF1/3 via WF1/2/3 none Logamatic 4323 - Technical specifications are subject to change without prior notice.
Heating zone data 11 11.24External pump fault message The function is disabled at the factory. You can select whether fault messages for a pump are displayed in this menu item. You can connect an external zero volt fault relay to terminals WF1 and WF2. If the contact is open a fault message is displayed. You can select between: 1. "none" 2.
11 Heating zone data 11.25Drying slab With this control panel you can enter a drying program for the slab if the heating system includes floor heating. "floor" must be set as the heating system. USER NOTE Check with your drying slab contractor for special requirements for drying slab drying prior to enabling this function. After a power failure, drying slab drying continues from where it was interrupted. Fig.
Heating zone data 11 The display shows the selected submenu. heatingzone data 2 drying slab no Hold down "Display" and turn the dial until the desired value appears (here: "yes"). + The display shows the set value. heatingzone data 2 Release "Display" to save your input. drying slab yes drying slab Input range Factory setting no yes no USER NOTE Parameters on the following pages enable you to select the temperatures and settings for the drying period.
11 Heating zone data Heat-up time By setting the "increase" parameter, you determine in which daily cycle the temperature should rise to dry out the drying slab. Turn the dial until submenu "drying slab increase" appears. The display shows the selected submenu. heatingzone data 2 drying slab increase daily + Hold down "Display" and turn the dial until the desired value appears (here: "every 5th day"). The display shows the set value.
Heating zone data 11 Set the holding time Here you can select a period of time for which the maximum temperature should be held to dry out the drying slab. Turn the dial until submenu "drying slab hold max temp" appears. The display shows the selected submenu. heatingzone data 2 drying slab hold max temp 4 days + Hold down "Display" and turn the dial until the desired value appears (here: "20 days"). The display shows the set value.
11 Heating zone data Set setback time By setting the "lowering" parameter, you determine in which daily cycle the temperature for drying the drying slab should be set back. Turn the dial until submenu "drying slab lowering" appears. The display shows the selected submenu. heatingzone data 2 drying slab lowering daily + Hold down "Display" and turn the dial until the desired value appears (here: "every 5th day"). The display shows the set value.
DHW data 12 12 DHW data In its standard version, the Logamatic 4323 control panel is not equipped with any DHW heating function. The following details regarding DHW data refer to the FM441 function module (accessory). 12.1 Selecting the DHW storage tank Here, you can log the DHW storage tank in and out if a DHW module is installed. If a cascade module is installed instead of a DHW module, you can select the type of hydraulic connection of the DHW storage tank. + Call up the service level.
12 DHW data 12.2 Set temperature range With this function you can set the upper limit for the desired DHW temperature. RISK OF SCALDING from hot water. WARNING! There is a risk of scalding if the desired DHW temperature is set higher than 122 °F (50 °C). z Do not draw off DHW unmixed. + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "DHW" appears. Press "Display" to call up a submenu (here: "DHW"). The display shows the selected submenu.
DHW data 12 12.3 Selecting switching optimization If you select the "optimization" function, DHW heating will begin prior to the actual start point. The control panel calculates the start time, taking into consideration the residual DHW storage tank heat and the start of heating for the heating zones, so that the DHW temperature is reached at the time you have selected (time switch). + Call up the service level. "general data" appears as the first main menu.
12 DHW data 12.4 Selecting residual heat use If you select the "utlz.leftovr.ht" function, you can also utilize the residual boiler heat for heating the storage tank. "Residual heat use yes" If you select "utlz.leftovr.ht yes", the control panel calculates the shutdown temperature of the burner and the primary pump runtime until the storage tank is fully heated up using the residual boiler heat. The burner is switched off before the set DHW temperature is reached.
DHW data 12 12.5 Setting differential With "differential" you can determine, at how many Fahrenheit (°F) (Kelvin (K)) below the set DHW temperature the reloading of the storage tank begins. + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "DHW" appears. Press "Display" to call up a submenu (here: "DHW"). The display shows the selected submenu. DHW data DHW yes Turn the dial until submenu "differential" appears.
12 DHW data 12.6 Increasing boiler temperature With the "raise boilr temp" function, you can determine the boiler water temperature during DHW heating. The boiler raising temperature is added to the desired DHW temperature and results in the desired supply temperature for DHW heating. The factory setting of 72 °F (40 °C) is optimized for rapid DHW heating. + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "DHW" appears.
DHW data 12 12.7 External fault message (WF1/2) An external zero volt fault message contact of a DHW primary pump or an inert anode can be connected to terminals WF1 and WF2 of FM441 module. – WF1 and WF2 contacts closed = no fault – WF1 and WF2 contacts open = fault + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "DHW" appears. Press "Display" to call up a submenu (here: "DHW"). The display shows the selected submenu.
12 DHW data 12.8 External contact (WF1/3) "loading once" or "disinfection" can be initiated (subject to setting) if a zero volt button is connected to terminals WF1 and WF3 in module FM441. The thermal disinfection switching program is disabled if "thermal disinfection" has been selected. "Loading once" If DHW heating has been switched off according to the switching times of the DHW program, you may start "loading once" with the button. The DHW recirculation pump starts simultaneously.
DHW data 12 The display shows the set value. DHW data external contact WF1/3 loading once Release "Display" to save your input. Press "Back" to return to the next level up. external contact Input range Factory setting loading once disinfection none none Logamatic 4323 - Technical specifications are subject to change without prior notice.
12 DHW data 12.9 Selecting and setting thermal disinfection If you select the "thermal disinfection" function, the DHW is brought to a temperature (158 °F (70 °C)) once or several times a week. This is high enough to kill off germs (e.g. legionella bacteria). The tank primary pump and DHW recirculation pump run constantly during the thermal disinfection process. If you have selected "thermal disinfection yes", thermal disinfection starts according to factory settings or your own preferences.
DHW data 12 The display shows the set value. DHW data thermal disinfection Release "Display" to save your input. yes Press "Back" to return to the next level up. thermal disinfection Input range Factory setting no yes no Logamatic 4323 - Technical specifications are subject to change without prior notice.
12 DHW data 12.10Setting disinfection temperature Via the "temperature disinfection" function, you can set the thermal disinfection temperature (Æ Chapter 12.9). RISK OF SCALDING from hot water. WARNING! + z If thermal disinfection is activated, ensure that a thermostatic tempering valve is installed as protection against scalding. Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "DHW" appears.
DHW data 12 12.11Setting day of week for disinfection The day of the week for disinfection can be set with the "day of week disinfection" function. USER NOTE The "day of week disinfection" function is not displayed if thermal disinfection was previously set using the "external contact WF1/3" function. + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "DHW" appears. Press "Display" to call up a submenu (here: "DHW").
12 DHW data 12.12Setting time of day for disinfection The time of day for disinfection can be set with the "time disinfection" function. USER NOTE The "time disinfection" function is not displayed if thermal disinfection was previously set using the "external contact WF1/3" function. . + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "DHW" appears. Press "Display" to call up a submenu (here: "DHW"). The display shows the selected submenu.
DHW data 12 12.13Daily heating When daily heat-up is set, the DHW (which may include a solar storage tank, if installed) is heated to 140 °F (60 °C) once a day to prevent legionella bacteria from multiplying in the DHW. The time when the storage tank is heated can be adjusted. + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "DHW" appears. Press "Display" to call up a submenu (here: "DHW"). The display shows the selected submenu.
12 DHW data 12.14Selecting the recirculation pump You can set DHW to be immediately available at the tap via the "recirculation" function. + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "DHW" appears. Press "Display" to call up a submenu (here: "DHW"). The display shows the selected submenu. DHW data DHW yes Turn the dial until submenu "recirculation" appears. The display shows the selected submenu.
DHW data 12 12.15Setting the recirculation pump intervals Interval operation reduces the operating costs of the recirculation pump. You can set DHW to be immediately available at the draw-off points using the "recirculation per hour" function. The set interval applies during the period when the time program enables the recirculation pump. This may be: – the factory-set recirculation pump program, – your own recirculation pump program, – a connection to the heating zone switching times.
12 DHW data Hold down "Display" and turn the dial until the desired value appears (here: "off"). The recirculation pump will now only operate during heating once. + The display shows the set value. DHW data recirculation per hour Release "Display" to save your input. off Press "Back" to return to the next level up. recirculation per hour 90 Input range Factory setting off 1 cycles 2 cycles 3 cycles 4 cycles 5 cycles 6 cycles constant oper.
Substations 13 13 Substations The Logamatic 4323 control panel with ZM433 central module can be operated with – address 0 (stand-alone), – address 1 (linked to a master, i.e. the control panel that provides externally generated heat) and with – address > 1 (as substation linked to other Buderus Logamatic 4000 control panels).
13 Substations 13.1 Setting the minimum warm up temperature This menu will only be displayed by the Logamatic 4323 control panel if address 0 or 1 has been selected. The heat consumers will only be supplied with heat if the set temperature has been exceeded, or no later than after the time set up under "maximum warm up time" has expired. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until the main menu "sub station" appears.
Substations 13 13.2 Setting the maximum warm up time This menu will only be displayed by the Logamatic 4323 control panel if address 0 or 1 has been selected, and the minimum warm up temperature and therefore also the warm up time have been enabled. Here, set the maximum time after which the heating zone pumps are started, even if "minimum warm up temp" has not been achieved within "maximum warm up time".
13 Substations 13.3 Setting boiler raising This menu will only appear when operating the Logamatic 4323 control panel as a substation (address > 1). The value entered here will be added to the heat demand of the control panel and thereby increases the demand temperature. This setting is recommended for compensating temperature losses in systems with long supply lines. + Call up the service level. "general data" appears as the first main menu. + Turn the dial until the main menu "sub station" appears.
Characteristic heating curve 14 14 Characteristic heating curve Using the "heating curves" menu, you can display the current heating curves of the relevant heating zones. The supply temperatures (ST), which depend on the outdoor temperature (OT), are displayed. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "heating curves" appears. The display shows the selected main menu.
15 Running relay test 15 Running relay test With the "relay test" menu, you can check whether you have correctly connected the external components (e.g. pumps). The displays depend on the installed modules. Depending on the current operating conditions, there may be a time delay between demand and display. SYSTEM DAMAGE through disabled functions. CAUTION! The heat supply of the heating system is not assured during the relay test. All functions are disconnected from the control.
Running relay test 15 Relay test example + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "relay test" appears. The display shows the selected main menu. service level relay test Press "Display" to call up a submenu (here: "heating zone 0"). The display shows the selected submenu. RELAY TEST heating zone 0 Turn the dial until submenu "heating zone 2" appears. The display shows the selected submenu.
15 Running relay test Turn the dial until submenu "actuator" appears. The display shows the selected submenu. RELAY TEST heating zone 2 actuator off + Hold down "Display" and turn the dial until the desired value appears (here: "closed"). The display shows the set value. RELAY TEST 2 heating zone 2 actuator closed Release "Display" to save your input. Press "Back" twice to return to the next levels up. This ends the relay test. This will also be the case when you close the flap.
Multi-boiler systems 16 16 Multi-boiler systems The Logamatic 4323 control panel, together with modules FM456 /457/458, can control multi-boiler systems (cascades). For a description of this function, see the technical documentation of the relevant module. Logamatic 4323 - Technical specifications are subject to change without prior notice.
17 Carrying out an LCD test 17 Carrying out an LCD test Using the "testing LCD" menu, you can check whether all symbols are fully displayed. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "testing LCD" appears. The display shows the selected main menu. service level testing LCD Press "Display". 8Ccd8X8beP The LCD is OK if all signs and symbols are correctly displayed. Press "Back" to return to the next level up.
Fault log 18 18 Fault log Using the "fault log" menu, you can display the last four fault messages of your heating system. The MEC2 can only display the fault messages of the control panel it is connected to. + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "fault log" appears. The display shows the selected main menu. service level fault log Press "Display". The fault message is displayed.
18 Fault log Fault displays The Logamatic 4323 can display the following faults, if in addition to the ZM433, the most frequently-used function modules FM441 and the FM442 are installed. – outdoor sensor – Addr.conflict x – supply sensor x – wrong module x – DHW sensor – unknown module x – DHW cold – inert anode – DHW warning – external fault – disinfection – insuff.
Fault 19 19 Fault Fault Effect on control characteristics Possible causes of fault Remedy outdoor sensor – The minimum outdoor temperature is applied. – Checks of the outdoor temperature sensor. – Check whether the outdoor temperature sensor is connected to the control panel with address 1 (for information regarding the position of the outdoor temperature sensor see Æ Chapter 5.1).
19 Fault Fault Effect on control characteristics Possible causes of fault remote control x – Because no actual room – Remote control incorrectly connected – Check remote control function and temperature is available, the or defective. connection. effects of the following features Replace remote control or module. are disabled: room effect, start – Incorrect address allocated to remote – Check remote control address and stop optimization, automatic control. (see BFU remote control adaptation.
Fault 19 Fault Effect on control characteristics Possible causes of fault Remedy unknown module x – All outputs are switched off from – This is a later module type, not the module and the recognized by the older control corresponding error LED is software. switched on. – Checking the control panel version in the MEC2 (Æ Chapter 21). If necessary, replace the CM431 and MEC. – Module or control panel is defective. – If necessary, replace module or control panel.
20 Monitor data 20 Monitor data Using the "act system data" menu you can display the set and actual values. The menus described in these instructions relate exclusively to the Logamatic 4211 control panel with the most commonly used FM441 and FM442 modules. Some display values are separated by a slash. The number in front of the slash specifies the set value of each corresponding parameter and the figure after the slash is the actual value.
Monitor data MONITOR HZ2 supply 140/138 68/66 Room night mode alwys 20 The set and actual values for the supply and room temperatures are displayed. The last line displays one of the following operating modes: – night mode alwys – day mode always – auto mode always – automatic day – vacation – summer – startopt – stopopt. – slab – DHW priority – no setback Turn the dial to scroll through the heating zone monitor data. Design temperature adaptation MONITOR design startopt stopopt.
20 Monitor data 20.2 DHW monitor data The "DHW" monitor menu can be used to display data for DHW settings. The displays depend on the settings that have been selected in the "DHW" function. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "act system data" appears. Press "Display" to call up a submenu (here: "heating zone 0"). The display shows the selected submenu. DISPLAY heating zone 0 Turn the dial until submenu "DHW" appears.
Monitor data 20 optimizd Indicates the period during which the system starts DHW heating before the actual set point, to achieve the set DHW temperature in good time. Rotate selector to scroll through the DHW monitor data. DHW loading MONITOR DHW DHW loading off recirculation on Indicates the operating condition of the tank primary pump. recirculation Indicates the operating condition of the DHW circulation pump. Press "Back" to return to the next level up.
20 Monitor data 20.3 Substation monitor data + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "act system data" appears. Press "Display" to call up a submenu (here: "heating zone 0"). The display shows the selected submenu. DISPLAY heating zone 0 Turn the dial until the desired submenu appears (here: "sub station"). The display shows the selected submenu. DISPLAY sub station Press "Display".
Display version 21 21 Display version Using the "version" menu you can display the MEC2 remote control version as well as that of the selected control panel. + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "version" appears. The display shows the selected main menu. service level version Press "Display" to call up a submenu. The versions for the MEC2 remote control and the control panel are displayed. version MEC controller 8.xx 8.
22 Selecting the control panel 22 Selecting the control panel With the "controller" menu you can select a control panel, if the MEC2 is operated offline, i.e. without connected control panel or with a separate power supply unit. + Call up the service level. "general data" appears as the first main menu. + Turn the dial until main menu "controller" appears. The display shows the selected main menu. service level controller Press "Display" to call up a submenu (here: "Logamatic 4321").
Reset to the factory settings 23 23 Reset to the factory settings USER NOTE With the "reset" menu you can change all settings of the operator or service levels back to their factory settings. Exception: The timer program is retained. 23.1 Resetting all control panel parameter settings All values are automatically reset. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "reset" appears. The display shows the selected main menu.
23 Reset to the factory settings 23.2 Resetting the fault log Using the "reset fault log" function you can reset the whole fault memory. This deletes all entries in the fault log. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "reset" appears. Briefly press "Display" to call up a submenu (here: "settings controller"). All settings may be lost if you press for too long. The display shows the selected submenu.
Reset to the factory settings 23 23.3 Resetting the service call Reset the service call after maintenance has been completed. This means that the service call is no longer shown when the flap is closed. USER NOTE The maintenance interval is restarted by resetting the service call. Note that in the case of service calls by date the next maintenance date is reset to one year ahead. + + Call up the service level. "general data" appears as the first main menu. Turn the dial until main menu "reset" appears.
24 24 Sensor characteristics Sensor characteristics z Isolate the heating system from the power supply before taking any readings. Using the diagram you can check whether temperature and resistance correlate. Fault test (without room temperature sensor) z Remove the sensor terminals. USER NOTE z Check the resistance at the sensor lead ends using an ohmmeter. For all curves, the sensor tolerance is up to 3 %/77 °F (25 °C). z Check the sensor temperature with a thermometer. Fig.
Sensor characteristics Fig. 19 24 Room temperature and emission temperature sensor 1 Room temperature sensor curve 2 Flue gas temperature sensor curve Logamatic 4323 - Technical specifications are subject to change without prior notice.
25 25 Index Index A I Actual room temperature . . . . Adaptation . . . . . . . . . . . Adjustable parameter . . . . . . Alternative type of control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 107 . 8 . 22 B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 . 42 . 41 . 29 Calling up main menus . . Calling up submenus . . . Calling up the service level Circulator . . . . .
Index 25 S S1 hook switch . . . . . . . . . . . . . . Scope of delivery . . . . . . . . . . . . Service call . . . . . . . . . . . . . . . . Service level . . . . . . . . . . . . . . . Set point adjustments . . . . . . . . . . Set the time . . . . . . . . . . . . . . . Set warm weather shutdown temperature Setback time . . . . . . . . . . . . . . . Setting addresses . . . . . . . . . . . . Setting the control panel address . . . . Slab . . . . . . . . . . . . . . . . . . . Software version . . . . . . . .