5.3.10 Checking the safety sensor connection lead
Check to ensure that all plug-in connections on the
sensor and UBA are in order. Note that an incorrectly-
inserted plug can lead to the generation of error
messages. Start up the boiler by pressing the “reset”
button.
z Set the power switch to “0”.
z Disconnect the system from the power supply.
z Unplug cable connection from flow sensor (fig. 60,
item 1).
z Disconnect 18-pin plug from UBA (fig. 60, item 2).
z Use a continuity tester to check the cable between
the plug-in connection and the 18-pin plug in the
UBA. The test should be carried out on connections
06-18 and 08-18 (fig. 60).
z If the cables are in order, plug them in.
z Connect system to mains power supply.
z Turn the power switch to “I”.
5.3.11 Checking the flow sensor
z Unplug cable connection from sensor.
z Measure resistance of sensor (fig. 61, item 1).
z Use a second-reading thermometer to measure the
temperature around the sensor.
z Compare readings with values shown in table 6. If
there is any mismatch (i.e. > 5%), the sensor is
defective.
z If the sensor is working correctly, plug it in once
more.