Technical data
Installation and servicing instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 02/2006 55
Subject to modifications resulting from technical improvements! Buderus • http://www.buderus-domestic.co.uk
Servicing 5
5.3 Checking and replacing parts
5.3.1 Checking the flue gas thermostat
z Detach plug-and-socket connection on cable to flue
gas thermostat. Ensure that no cable is earthed
(grounded) at any point.
z Allow the flue gas thermostat to cool down. Activation
temperature: Buderus 600 - 11R / 19R / 24R: 105 °C
z Check flue gas thermostat for continuity. If continuity
is not present, the flue gas thermostat is defective.
z Replace any flue gas thermostat found to be defec-
tive. Ensure you use only genuine Buderus spare
parts.
z If the flue gas thermostat is working correctly, plug it
in once more.
5.3.2 Replacing the flue gas thermostat
z Unscrew the flow-backup mounting.
z Detach the cable plug at the flue gas thermostat.
z Loosen both retaining screws on the flue gas thermo-
stat.
z Remove the flue gas thermostat and replace with a
new unit (fig. 48).
z Retighten the retaining screws.
z Reconnect the cable plug.
z Screw the mounting into place.
5.3.3 Replacing the UBA
z Disconnect the system from the power supply.
z Loosen the two screws on the UBA (fig. 49, item 1).
z Carefully turn the UBA around with the backside
facing up (fig. 50).
z Note the position of the cable plugs, disconnect all
cable plugs.
z Fit a new UBA.
z Reconnect all plug-in cables to their correct sockets.
z Turn the UBA around and place back onto the
bracket.
z Tighten the two screws.
z Connect system to mains power supply.
Fig. 48 Buderus 600 - 11R / 19R / 24R :
replacing the flue gas thermostat
Fig. 49 Replacing the UBA
1
Fig. 50 Backside of the UBA