Technical data

36 Installation and servicing instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 02/2006
Buderus • http://www.buderus-domestic.co.uk Subject to modifications resulting from technical improvements!
Commissioning2
2.2.7 Setting the heating capacity
z Open the cover to the 2nd operating level (fig. 31,
item 1).
z Set the heating capacity (table 5), according to the
amount of heat output required for the system
(fig. 31, item 4).
Controller setting Flow temperature [°C]
1
40
2
44
3
48
4
53
5
58
6
62
7
67
8
71
9
76
10
80
table 4 Flow temperature
Controller
setting
Heating capacity [kW] (±5 %)
11 R 19 R 24 R
14.99.79.7
2 5.6 10.7 11.3
3 6.3 11.8 12.9
4 6.9 12.8 14.5
5 7.6 13.8 16.0
6 8.3 14.9 17.6
7 9.0 15.9 19.2
8 9.6 16.9 20.8
9 10.3 18.0 22.4
10 11.0 19.0 24.0
table 5 Heating capacity
NOTE
The controller is factory-adjusted to
setting “6”.