User's Manual
Features:
‐ RemoteOn/Offcontrol
‐ ManualOn/Offcontrol
‐ Abilitytocreateagroupofdevices
‐ Abilitytomonitorpowerconsumption
‐ LEDindicatorstoshowthestateoftheswitch
On/OffControl:
‐ RemoteControl:
o TheBudderflyswitchescanbecontrolledremotelythrutheBudderflysoftware.
o The
Budderflysoftwarewillinformyouthattheactionwassuccessful.Incasetheaction
failed,pleaserepeattheprocedure
‐ Manual Control: In addition to the Rem ote control, the Budderfly switches can be
controlledmanually.Tapthetoporbottomoftherockertogglethestateconnectedload.
DeviceGrouping:
‐ UsingtheBudderflywebapplication,itispossibletocreateaGroupofdevicesthatcanbe
controlledremotelysimultaneouslywithjustoneclick.
‐ Budderflyswitchescanjoin/disjoingroupsatanytime.
Powerconsumption:
Budderfly switches will measure the current, the voltage and the power consumed by the
connected
load,andwillstoretheminimum,maximumandaveragedataforthepast7days.
The data can be accessed at any time thru the Budderfly software. The user can generate
reports,monitortheconsumptionorcheckexpenses.
LEDIndicators:
TheBudderflyswitchesareequippedwith2LEDsthatwill
indicatethestateofthedevice.
‐ PowerLED:
o Color:Red
o State:
Off:Budderflyswitchisnotpowered.
On:Budderflyswitchispoweredandcanbecontrolledremotely.
Blinking:Budderflyswitchispowered,butthe“PowerCut‐off”modeisactivated.
‐ GroupLED:
o Color:Green
o State:
Off:Budderflyswitchisnotmemberofagroup.
On:Budderflyswitchismemberofagroup.
Blinking: Budderfly switch is joining a group (Blinking state duration is less than 1
second).
Reset:
Ifthedevicestopsresponding,itcanberestarted
bypushingtheResetButton.Anon‐metallic
pinshouldbeusedtopushtheresetbutton.
Noneofthestoredparametersareaffected.
“PowerCut‐Off”mode:
‐ TheBudderflyswitcheshavetheabilitytocompletelydisconnectthepowerfrom
theload.
‐ Pressing the top of the rocker for 15 seconds will activate the “Power Cut‐off”
feature;theloadwillbeturnedoff.
‐ ThePowerLEDwillstartblinkingtoindicatethat theloadis
disconnectedandthe
switchisinthePowerCut‐offmode.
‐ When the “Power Cut‐off” mode is activated, the sw itch cannot be turned on
throughsoftwareandcannotbeturnedonphysically.
‐ Pressingthebottomoftherockerfor15secondswillde‐activatethe“PowerCut‐
off”
mode,andthedevicewillgobacktothenormalstate.
Communication:
The Budderfly Dual Band Outlets use the power line and radio frequency to
communicatewiththe“FacilityController”.
Theoutletscanreplytothefollowingcommands:
• Join/Disjoingroup“X”:TheoutletwillJoin/Disjointhegroup”X”.Eachoutletcanbe
amemberofseveralgroupsatthesametime.
•
Direct RTC synchronization: The outlet can receive a command to synchronize its
“RealTimeClock”
• Get Actual Measurement: When the outlet receives a “Get Measurement”
command,itwillsendbacktothefacilitycontrollerastringofdatathatcontains:
‐ TheCurrentinAmpere“A”.
‐ ThePowerin
Watt“W”.
‐ ATimestamp.
• Get Stored Measurement: The outlet will send back to the Facility Controller the
storedelectricalmeasurements.
• DirectResetCommands:Theoutletcanreceive3typesofresetcommands:
‐ Hard Reset: This command will restart the device without affecting any stored
parameter.
‐ DataReset:
Thisc ommandwilleraseallthemeasurementandRTCdatastoredin
thenon‐volatilememory.
‐ DisjoinGroup:Thiscommandwillremovethedevicefromallthejoinedgroups.
• GroupResetCommands:Theabove reset commandscanbe directedtoagroupof
devicesinsteadofjustonedevice.
Specifications:
Power:120V‐277VAC/60Hz
MaximumLoads:
o 120VAC,60Hertz:1600WforTungsten,1400WforElectronicballast,800Wfor
Standardballast
o 277VAC,60Hertz:3300WforElectronicballast,1200WforStandardballast.
NeutralLine:Required
OperatingTemperature:10
o
Cto+40
o
C
Certification:UL&FCCcertificationisinprogress
Forindooruseonly
Warranty:
BudderflyLLC warrantstotheoriginalconsumerpurchaserandnotforthebenefitof
anyoneelsethat this product atthetimeof its sale by Budderflyisfreeof defects in
material and workmanship under normal and proper use for a period of three (3)
years from date of delivery to
you.Budderfly’s only obligation is to correct such
defects by repair or replacement, at its option, if within such three ye ar period the
product is returned prepaid via Budderfly’s Returned Materials Authorization (RMA)
process to Budderfly LLC, Att: Quality Assurance Department, 2 Trap Falls Road,
Suite 507, Shelton, CT 06484.In no
case is product to be returned without first
obtaininganRMA.
This warranty excludes and there is disclaimed liability for labor for removal of this
productorreinstallation.Thiswarrantyisvoidifthisproductisinstalledimproperlyor
inan improperenvironment,overloaded,misused, opened, abused, oralteredin any
manner,or
is not used undernormal operating conditionsor notin accordance with
any labels or instructions.There are no other or implied warranties of any kind,
including merchantability and fitness for a particular purpose, but if any implied
warranty is required by the applicable jurisdiction, the duration of any such
implied
warranty is required by the applicable jurisdiction, the duration of any such implied
warranty, including merchantability and fitness for a particular purpose, is limited to
threeyears.Budderflyisnotliableforincidental,indi rect,special,orconsequential
damages,includingwithoutlimitati o n,damageto,orlossofuseof,anyequipment,
lost
sales or profits or delay or failure to perform this warranty obligation.
Budderfly’sliability on any claim for damages a rising outof in connection with the
manufacture, sales, installation delivery, or use of the product shall never exceed
the purchase price of the product. The remedies provided herein are the exclusive
remedies
underthiswarranty,whetherbasedoncontract,tortorotherwise.
WARNING–ELECTRICALSHOCKHAZARD
• Neveruseametallicpintopresstheresetbutton.
WARNING–ELECTRICALSHOCKHAZARD
WhenreplacingtheBulbs,makesuretoenablethe“PowerCut‐off”
mode.IfthepowerLEDdoesnotstartblinking,pleaseconsultaqualified
electrician.
Specifications subject to
change without notice
duetocontinuingproduct
improvement