Installation Guide
Page 6 
Floor Protection: or Hearth Protector  
Floor protection must be 3/8” minimum thickness non-combustible material or equivalent. 
How to use alternate materials and how to calculate equivalent thickness. 
An easy means of determining if a proposed alternate floor protector meets requirements listed 
in the appliance manual is to follow this procedure: 
1.  Convert specification to R-value: 
 R-value is given—no conversion is needed. 
 K– factor is given with a required thickness (T) in inches: 
 C-factor is given: R=1/C 
2.  Determine the R-value of the proposed alternate floor protector.  
 Use the formula in step (1) to convert values not expressed as “R” 
 For multiple layers, add R-values of each layer to determine the overall R-value. 
3.  If the overall R-value of the system is grater than the R-value of the specified floor 
protector, the alternate is acceptable. 
Example: 
The specified floor protector should be 3/4” thick material with a K-factor of 0.84. 
The proposed alternate is 4” brick with a C-factor of 1.25 over 1/8” mineral board with a  
K-factor of 0.29. 
Step (a): Use formula above to convert specification to R-value. R= 1/K x T = 1/0.84 x .75 = 
 0.893 
Step (b): Calculate R of proposed system. 4” brick of C=1.25, therefore Rbrick = 1/C = 1/1.25  
 =0.80 1/8” mineral board of K = 0.29, therefore Rmin.bd. =1/029 x0.125 = 0.431  
Step (c): Compare proposed system R of 1.231 to specified R of 0.893. Since proposed 
 system R is greater than required , the system is acceptable. 
Definitions: 
 Thermal conductance = C = Btu = W 
 (hr)(ft²)(°F) (m²)(°K) 
 Thermal conductance = K = (Btu)(inch) = W = (Btu) 
 (hr)(ft²)(°f) (m)(°K) (hr)(tf)(°F) 
 Thermal conductance = R = (ft²)(hr)(°F) = (m²)(°K) 
 Btu W 
Install in accordance with 24 CFR, Part 3280 (HUD). 










