Installation manual

Quick
con guration
If the Temperature control function is used to manage a simple system there
is no need to interact with the control unit via “Confi gure zones” in the
“Maintenance” menu – just insert the confi gurators in the devices. A simple
system is defi ned as a system which for each zone has just one actuator for
heating and/or one actuator for cooling.
In essence a simple zone has an actuator which only controls ON/OFF loads
(solenoid valves, pumps, single-speed fan-coils and electric radiators). Only
one circulation pump can be operated for the whole system. The sensor is
always confi gured by inserting two confi gurators which identify the number
of the zone controlled in sockets [ZA] and [ZB]. If necessary socket [SLA] can
[MOD] = 0
[ZA] = 3
[ZB] = 3
[N] = 1
[ZA] = 3
[ZB] = 3
BUS
HEATING ONLY ZONE
Sensor confi guration:
insert confi gurator 0 in socket [MOD];
insert the confi gurators corresponding to the zone number in sockets [ZA]
and [ZB].
also be confi gured to defi ne the master or slave function, socket [P] for the
pump management mode and socket [DEL] for the pump switching on delay.
Confi guring socket [MOD] defi nes whether the zone manages a heating,
cooling or mixed system.
Depending on the function required, the corresponding actuator must
be confi gured, as well as the sensor [MOD] socket. For the confi guration
operation follow the procedure described below.
Actuator confi guration:
insert confi gurator 1 in socket [N];
insert the confi gurators corresponding to the zone number (the same as
those inserted in the sensor) in sockets [ZA] and [ZB].
[MOD] = 1
[ZA] = 3
[ZB] = 3
[N] = 2
[ZA] = 3
[ZB] = 3
BUS
COOLING ONLY ZONE
Sensor confi guration:
insert confi gurator 1 in socket [MOD];
insert the confi gurators corresponding to the zone number in sockets [ZA]
and [ZB].
Actuator confi guration:
insert confi gurator 2 in socket [N];
insert the confi gurators corresponding to the zone number (the same as
those inserted in the sensor) in sockets [ZA] and [ZB].
N
L
C1
C2
N
L
C1
C2
41
TECHNICAL FEATURES
CATALOGUE MY HOME TEMPERATURE CONTROL