Unit installation
75
In addition activation of a PA zone when the system is unset or part set causes the
Intruder outputs to activate. Two Dual zone activations will also cause the In-
truder outputs to activate when the system is full set. For details on Dual Zones
see Section 5: MENU OPTIONS; Option 7: Zones; Zone Functions and for de-
tails on full sets and part sets see Section 4: SETTING OPTIONS.
When activated, the output latches on until a code authorised for Intruder Reset
is entered, refer to Section 5: MENU OPTIONS; Option 4: Codes and Option 6:
Parameters; 7 Reset.
The Intruder output is not subject to Re-arm or Bell Delay.
By default the Intruder output is not activated on a part set system. For Intruder
output activation when the system is part set enable the Part Intruder option. See
Section 5: MENU OPTIONS; Option 6: Parameters; 6 User options; 4 Part In-
truder
.
4 Set
The Set output type is a reflex output activated when the system is full set.
The Set output does not, by default, activate when the system is part set. To
activate the Set output during a part set the part set attribute must be enabled, see
Section 5: MENU OPTIONS: Option 6 – Parameters; 06 User Options; 08 Part
Set
.
5 Bells
The Bells output type is activated in a full alarm condition, it is subject to Bell
Time, Bell Delay and re-arm, for programming details see Section 5: MENU OP-
TIONS; Option 6 – Parameters.
To prevent the Bells outputs from activating when the system is part set the Part
Bells option must be disabled (enabled by default), see Section 5: MENU OP-
TIONS; Option 6 Parameters; 6 User Options; 3 Part Bells.
6 Strobe
The Strobe output type is activated in a full alarm condition, it is subject to Bell
Time, Bell Delay and Re-arm parameters, for programming details see Section 5:
MENU OPTIONS; Option 6: Parameters
. The Strobe output type can be disabled
from re-arm allowing it to operate continuously following a full alarm condition.
To prevent Strobe outputs from activating when the system is Part Set the Part
Bells option must be disabled (enabled by default), see Section 5: MENU OP-
TIONS; Option 6: Parameters; 6 User Options; 3 Part Bells.
7 Switch DC
The Switch DC output type is not activated by any zone types or alarm condi-
tions. It is used to power detectors that require a momentary power interruption to
reset them when the system is setting — for example, break-glass detectors and
vibration detectors). The Switch DC is a 0 V output that pulses to +12 V for two
seconds when the (Full or Part) setting procedure is initiated and then returns to
0 V.
8 = Outputs (cont’d)