Unit installation
61
04 Part Intruder
When enabled this parameter will activate Intruder outputs if an alarm condition
occurs when the system is Part Set.
05 PA Delay
When enabled this parameter delays the activation of PA outputs, after the
activation of a PA or PA Silent zone, by 30 seconds.
Note: This does not affect star key PA operation (Ö2).
06 Instant Key 0
When enabled key 0 on the keypad will act as a Push-to-Set button. See
Section 4: SETTING OPTIONS; Silent Setting.
07 Abort and Star Abort
Normally when the Intruder reset parameter is Enabled only a valid code with
the Reset parameter enabled may reset an Intruder alarm. The Abort/Star Abort
feature allows users, without the Reset feature on their code enabled, to cancel
and reset an Intruder alarm under certain conditions. The Abort feature has two
modes of operation: Abort and Star Abort, these are outlined below.
When programming the Abort parameter pressing the Ö key toggles between
Abort and Star Abort, pressing the # key enables/disables the Abort feature.
The Abort parameter is, by default, disabled. Enabling the Abort feature
defaults to Star Abort mode. Press ent to accept the programming or esc to
cancel.
Notes: The Abort/Star Abort feature only affects the system if the Intruder Reset
parameter is enabled, see Section 5: MENU OPTIONS; 6 – Parameters;
07 Reset; 1 Intruder.
The Abort/Star Abort feature does not operate when an Intruder alarm is
caused when the system is set. The system must first be unsetting.
The Abort time is fixed at 90 seconds.
Abort Time
When enabled the Abort feature gives a 90 second time period during which
any user code (regardless of whether it has the Intruder Reset attribute enabled
or not) may reset an Intruder alarm.
• If an Entry Time-out occurs or if the user(s) stray from the Entry Route and
cause an Intruder alarm then the Bell, Strobe and Intruder outputs all
activate.
• Entering any valid user code, within the Abort Time (90 s) cancels the
activation of the Bell, Strobe and Intruder outputs.
After the Abort Time has elapsed a code without the Intruder Reset attribute
enabled will cancel the Bell and Strobe outputs but the Intruder outputs will not
be deactivated. The system requires to be reset by entering a code with the
valid reset attributes enabled. If Remote Reset is enabled the system prompts
for a Technistore code.
6 = Parameters (cont’d)