Instruction manual

1070 072 163-101 (97.11) GB
BTSMADAP & BTS_ZV Function Modules 5-5
Bit Cause of Fault Troubleshooting
9 Cascade number not per-
mitted with manual diag-
nostics.
Parameter P2 of DIAG500E module
is not within permitted range be-
tween 1 and 64.
Modify parameter settings.
8 Invalid number of cascade
sequences.
Parameter P3 of DIAG500E module
has a value higher than 64. You cannot,
however, process more than the maxi-
mum of 64 cascade sequences.
Modify parameter settings.
7 Fault in system area (sys-
tem instruction).
This bit indicates that too many system
instructions (e.g. LAD and TAD) are
being used in the entire PLC program.
Reduce the number of system in-
struction calls or utilize sequential call
coordination.
In this context, see also the manual
entitled CL500 System Instructions,
order no. 1070 072 068.
6 Structural fault in cascade
sequence jump distributor.
The DIAG500E module has detected
a structural fault in the jump dis-
tributor for the cascade sequence.
The cause may be that the step
sequence in the jump distributor
does not correspond to that in the
step program.
Modify the step sequence either in
the cascade module or in the jump
distributor.
5 Data field address (P7) too
high.
The data field base address has
been defined too high, denying the
requested substations needed space
in the data field area.
Define a smaller start address.
4 Too many conditions in the
branch to be diagnosed.
In the BEFA command output or
WSB step-on condition branch, the
maximum number of 64 conditions
per BEFA or WSB allocation was
exceeded.
Divide the branch into several
subbranches.