Instruction manual
1070 072 163-101 (97.11) GB
BTSMADAP & BTS_ZV Function Modules5-4
Parameter P1 is used to establish the reference to the movement
screens. The base address is defined as the decimal constant of the
markers used in the movement screens. As a default, the BT-MADAP
module uses the markers from M180 upward. Accordingly, the following
applies to P1:
• P1 K180
P2 -DIAG500E
Symbolic address of DIAG500E diagnostic module that is internally called
from within the BTSMADAP module.
5.3.3 DIAG500E Diagnostic Messages
Data word DM254/D510 is used to return the messages of the DIAG500E
diagnostic module.
The messages comprise fault messages that cannot be entered in the
cascade data module in data word D0. The status word has the following
meaning:
Bit Cause of Fault Troubleshooting
15 Group fault indication. At least one of the following faults,
except bit 0, is present:
14 No significance.
13 Number of main station
cascades (P6) > Total
number, cascades (P3).
Number of main station cascades
(P6) > Total number, cascades (P3).
→Correct the parameterization.
12 Data module for cascade
not available or too short.
The DIAG500E module attempts to
diagnose a cascade sequence but is
either unable to find the corre-
sponding data module, or module is
incomplete.
→Link data modules of correct
length with the program.
11 No free memory capacity
in data field.
BOSCH standard modules occupy
blocks in data fields. A total of 12
data field blocks are available.
→Reduce the total number of call-
ups of BOSCH modules.
10 Step number too high. The step number to be diagnosed is
128. You may have selected a num-
ber larger than 128 in the Manual
mode of the cascade sequence.