Instruction manual

1070 072 163-101 (97.11) GB
BTSMADAP & BTS_ZV Function Modules5-2
5.2 BTSMADAP Function Module for CL200
5.2.1 Prerequisites and Allocations
Hardware:
BT5, variant HF000040 and up
BT20, variant HB000400 and up
ZE200, version 1.1 and higher, type 1 front panel
Software:
TesiMod, version 4.0 and higher
KETTE200, version 1.1 and higher
Allocations:
Counter: C0
Scratch markers: M188 through M191
BT Markers, M178 through M188
Data field, DF8196 through DF8190
5.2.2 Description of Parameters
CM -BTSMADAP,2
; +---+
P0 W -Kett_Anz ; < ! Number corresponds to the last cascade number
P1 W -K200 ; < ! KETTE200 module number as a constant
; +---+
Fig. 5-1 Call-up of BTSMADAP Function Module for CL200
P0 -Kett_Anz
At this point the number of the last cascade sequence is entered in the
form of a decimal constant. Gaps in the cascade sequence numbers are
permitted.
Example: Cascade sequences 1 through 5, 7, and 10 through 15 are
available. Therefore, parameter P0 is structured as follows:
P0 word K15
P1 K200 (delete "-" symbol)
Absolute address as decimal constant of the KETTE200 function module
which is internally called from within the BTSMADAP module.