Instruction manual
1070 072 163-101 (97.11) GB
CL350 / CL400 / CL500 Control Functions4-20
Movement Screen and Data Module Assignments:
Movement screen 211 -> DM1, D32
Movement screen 212 -> DM2, D32, and so forth.
D0 Data Word Assignment
Bit Fault and/or Status
message
Fault Correction
15 Structural fault in step
module
The structure of the jump distributor does not correspond with the programmed
step sequence. Step sequence runs correctly but diagnostics not possible.
→ Correct the program structure.
14
13
12
11
10
9
8
7
6
5
4
3 Jump instruction fault The 1st instruction in the step module must be the following jump instruction:
SP [A]
Between this and the 1st jump destination, for example:
-S1
only the jump instruction or comment lines may be inserted.
Attention Networks!
→ Check and correct program code.
2 Reference list The available module is faulty.
→ Recompile and reload program.
1 Step module (PB) not
available
The function module assigned by a defined data module is not available.
→ Ensure that module is linked.
0 Number of steps too
high or zero
Number of steps must be between > 0 and
≤ .
→ Check and correct program code.
Fig. 4-11 Fault Word in CL400 / CL500 Cascade Data Module
Interpretation of Wait and Monitoring Time (D18, D20)
At the point of entry into a new step, the KETTE200 module checks
whether the actual values for wait and monitoring time (D18, D20) have
been set by the application program. In the case of values
≠ 0
dec
, these
will be interpreted as valid times for the active step. If this is not the case,
the time default values are taken from parameters P2 and P3 of the
KETTE cascade management module.