CL350 / CL400 / CL500 Control Functions 4-15
D9.1 Synchronization Not Possible
The synchronization conditions:
BEFA = 1
bin
, and
WSB = 0
bin
are not met in or by any step.
D9.2 More Than One Sync Step
In the process of synchronizing in Automatic mode, more than one step
was found in which the conditions BEFA = 1
bin
and WSB = 0
bin
were true.
The synchronized start of the Auto Continue automatic mode is not possi-
ble.
D9.3 Cascade Data Module Generated
If D9.3 = 1
bin
is true, this indicates that the learning cycle or generation of
the cascade data module has been concluded.
Fault Pulse
Returns a pulse for a PLC cycle in the event that a fault was detected.
Fault criteria are as follows:
Reset fault marker
or
Expired monitoring time.
D9.7 Static Fault Signal
Returns a static signal in the event that a fault was detected (criteria
similar to D9.6).
The bit is reset by:
Fault acknowledgement
or
an action subsequent to a change of operating mode (e.g. Set Step
in Manual mode).