CL350 / CL400 / CL500 Control Functions 4-13
D7.7 Acknowledge
Fault acknowledgement
If this bit is set, an occurring cascade fault must be acknowledged by bit
D6.6.
If D7.7 is reset, and the WSB step-on condition is satisfied, the cascade
will auto-acknowledge.
4.4.5.1 OpMode Bit Priorities
If several operating mode bits are selected simultaneously in data word
D6 of the cascade sequence, processing is subject to the following priority
ranking:
1. Reset highest priority
2. Halt ↓
↓↓
↓
3. Start ↓
↓↓
↓
4. Manual ↓
↓↓
↓
5. Inching ↓
↓↓
↓
6. Automatic lowest priority
Fig. 4-7 OpMode Mode Priorities
4.4.6 D8 — OpMode Message
The D8 data word of each cascade data module contains the return mes-
sage indicating the operating mode that is enabled once the KETTE cas-
cade management module has been processed.
D8 nnBaMldg
D8.0 Manual mode H
D8.1 Inching mode T
D8.2 Automatic mode
A
D8.3 Start for all operating modes s
D8.4 Automatic or Inching mode enabled
D8.5 Synchronization in progress
D8.6 Wait time elapsing
D8.7 Reset, cascade is reset
r
D9.0 Halt, cascade is halted h
D9.1 No synchronization possible
D9.2 More than one step with BEFA = 1
bin
, synchronization
D9.3 Cascade data module generated
D9.4
D9.5
D9.6 Fault pulse
D9.7 Static fault
Fig. 4-8 D8 — Reported OpMode
D8.0 Manual Mode
The cascade is in Manual mode.
Confirmed by display of symbol H in cascade information of operator ter-
minal.