CL350 / CL400 / CL500 Control Functions 4-9
4.4.4 Automatic Mode
Function
Automatic processing of steps in accordance with conditions in the auto-
matic branches.
The command output is enabled when
• the conditions of the automatic branch have been met (BEFA =
1
bin
, and WSB = 0
bin
), and
• when the start (D6.3 ) = 1
bin
.
The command output occurs via the data bits of data words D80 through
D94 of the associated cascade data module (see cascade data module).
If the WSB (step-on conditions) = 1
bin
, the automatic step-on occurs.
Programming
Automatic mode (D6.2) and Start (D6.3) bits to be statically set to 1
bin
.
Diagnostics
Display in cascade information indicates A for Automatic mode at the cor-
responding cascade sequence.
Display of all criteria of the manual branch, either of the non-executed
BEFA or of the WSB branch.
The faulty cascade sequence is displayed.
Monitoring and wait time elapse with the default nominal values.