CL350 / CL400 / CL500 Control Functions4-4
4.3.3 KETTE Parameter Description
NOTE: No scratch markers belonging to the range indicated below may be
used as parameters.
CL400/CL500 M230.0 - M255.7
P0 W -PM/DM (Input parameter)
Via parameter P0, the KETTE cascade management module receives the
current cascade number n for the following modules:
Number of step module SCHRKn
Number of cascade data module DMn
Each cascade sequence n being processed utilizes a cascade data mod-
ule to store variable data, e.g. current step, monitoring time and wait time.
P1 W -BETR (Input parameter)
This parameter is used to transfer the selected OpMode (operating mode)
to the KETTE module:
P1.0 Manual mode (H)
P1.1 Inching mode (T)
P1.2 Automatic mode (A)
P1.3 Start
P1.4 S + 1
P1.5 Set Step
P1.6 Halt acknowledgement
P1.7 Reset
P1.8 Halt
P1.9 Synchronize
P1.10
P1.11 Generate cascade data module
P1.12 No step-on in same cycle
P1.13
P1.14 WSB does not reset BEFA
P1.15 Fault acknowledgement
The KETTE cascade management module writes the OpMode data into
data word D6 (nnBAWAHL) of the associated cascade data module.
When in Manual mode (H), the Start and Set Step command value is
transferred only upon actuating the movement keys on the operator ter-
minal.
P2 W -KUE (Input parameter)
Parameter P2 is used to transfer the value for the monitoring time to the
KETTE cascade management module. Unless it is again defined within
the individual steps, this value will remain the same for every step.
The time base is always 100 ms. For example, a default value of
P2 W K20D
will result in a monitoring time of 20 x 100 ms = 2 seconds