CL200 Control Functions3-14
3.4.5.1 OpMode Bit Priorities
If several operating mode bits are selected simultaneously in data word
D6 of the cascade sequence, processing is subject to the following priority
ranking:
1. Reset highest priority
2. Halt ↓
↓↓
↓
3. Start ↓
↓↓
↓
4. Manual ↓
↓↓
↓
5. Inching ↓
↓↓
↓
6. Automatic lowest priority
Fig. 3-7 OpMode Mode Priorities
3.4.6 D8 — OpMode Message
The D8 data word of each cascade data module contains the return mes-
sage indicating the operating mode that is enabled once the KETTE200
function module has been processed.
D8 nnBaMldg
D8.0 Manual mode H
D8.1 Inching mode T
D8.2 Automatic mode
A
D8.3 Start for all operating modes s
D8.4 Automatic or Inching mode enabled
D8.5
D8.6 Wait time elapsing
D8.7 Reset, cascade is reset
r
D9.0 Halt, cascade is halted h
D9.1
D9.2
D9.3
D9.4
D9.5
D9.6 Fault pulse
D9.7 Static fault
Fig. 3-8 D8 — Reported OpMode
D8.0 Manual Mode
The cascade is in Manual mode.
Confirmed by display of symbol H in cascade information of operator ter-
minal.
D8.1 Inching Mode
The cascade is in Inching mode.
Confirmed by display of symbol T in cascade information of operator ter-
minal.
D8.2 Automatic Mode
The cascade is in Automatic mode.
Confirmed by display of symbol A in cascade information of operator ter-
minal.