Instruction manual
1070 072 163-101 (97.11) GB
CL200 Control Functions 3-13
D7.4 Step Sequencing
No step-on effected within the same cycle.
Automatic mode only.
• If D7.4 = 1
bin
, only one step is processed per each PLC cycle.
• If D7.4 = 0
bin
, the satified WSB step-on condition causes the sub-
sequent step within the same cycle to be activated.
D7.6 WSB does not reset Command Output (BEFA)
2
Manual mode only.
• If D7.6 = 1
bin
, a satisfied WSB step-on condition will not reset the
associated BEFA command output.
• If D7.6 = 0
bin
, a satisfied WSB step-on condition will cause the
BEFA command output to be reset.
D7.7 Acknowledge
Fault acknowledgement
If this bit is set, an occurring cascade fault must be acknowledged by bit
D6.6.
If D7.7 is reset, and the WSB step-on condition is satisfied, the cascade
will auto-acknowledge.
2
This option applies to the CL200 with firmware version 1.5 and higher.