Instruction manual
1070 072 163-101 (97.11) GB
CL200 Control Functions3-12
D6.4 S+1
Execute the subsequent step.
In INCHING mode, a positive transition of this bit and satisfied step-on
condition (WSB = 1
bin
) will cause the next step to be executed.
In SEMI-AUTOMATIC mode, a positive transition of this bit, satisfied step-
on condition (WSB = 1
bin
), and with -HALBAUTO marker set, cause the
subsequent cascade sequence to be processed up to the reset -
HALBAUTO marker.
D6.5 Set Step
Accept preselected step number.
In MANUAL mode, the step prepared in D14 is transferred to the active
step (D12), and subsequently processed.
D6.6 Halt Acknowledgement
Manual fault acknowledgement.
Effective only if D7.7 = 1
bin
(manual fault acknowledgement).
A positive transition on this bit acknowledges a fault (cascade halted) that
was triggered by an expired monitoring time or by the reset fault marker.
Monitoring and wait times are loaded with the defined values but not
started.
D6.7 Reset
Cascade is reset.
D6.7 = 1
bin
triggers the following actions:
• Deletion of active step
• Reinitialization of cascade sequence
Subsequent to Reset, step 1 is prepared.
D7.0 Halt
Halt cascade sequence processing.
When the bit is set, the cascade is halted, and processing of the current
step continues. For D7.0 = 1
bin
, the following applies:
• BEFA is output
• monitoring time is halted
• wait time is halted