1070 072 163-101 (97.11) GB
CL200 Control Functions 3-5
3.3.3 BTSMADAP Parameter Description
NOTE: No scratch markers belonging to the range indicated below may be
used as parameters.
M188.0 - M191.7
P0 W -Kett_Anz
(Input parameter)
Via parameter P0, the BTSMADAP function module receives the number
n of the last cascade sequence for sequence processing as well as diag-
nostics.
Each cascade sequence being processed utilizes a cascade data module
to store variable data, e.g. current step, monitoring time and wait time.
P1 W -K200
(Input parameter)
This parameter specifies the module number of the KETTE200 function
module. It corresponds to the function module number in the symbol file.
Subsequent to calling the parameter list, the
"-" symbol character must be deleted. Using K200, the PM200 function
module number is assigned to the KETTE200 function module.
3.3.4 Register Contents
The PLC registers A, B, C, and D, plus the control flags (e.g. RES, Carry)
are not retained beyond the module call. Upon returning from the
BTSMADAP to the calling module, the registers will contain the contents
that are defined as listed in the following table.
Reg. Contents
A Version number of BTSMADAP module.
B Module release date.
C No relevance.
D No relevance.
Fig. 3-4 BTSMADAP Module, Register Contents