Instruction manual

1070 072 163-101 (97.11) GB
CL200 Control Functions3-2
3.2.2 Markers
Within the range of available markers, the markers listed below are as-
signed a permanent function.
Symbol Ad-
dress
Function
CL200
BEFA M191.0 Assigned to command output
WSB M191.1 Assigned to step-on function
STOEM M191.2 Fault marker; fault is indicated by STOEM = 0
bin
HALBAUTO M191.4 Step-on in Inching mode also without S+1 transition
WZT_HLT M191.5 Wait time stop
WZT M191.6 Wait time status 0
bin
: Wait time running
1
bin
: Wait time expired
M191.7 Monitoring time check.
If UEKONTR = 1
bin
, expiration of monitoring time will not trigger diagnostic function.
VERZW M188 Branch address (word)
Step number within the cascade to which branching is to take place if WSB = 1
bin
.
Fig. 3-1 CL200 Control Functions, Marker Definitions