Installation manual

Keypad/ Door Station Problems
“Communications Failure”
Home LED blinks and “Communication Failure, ID followed by the ID
number is reported upon user sign-in. This means that a Keypad or
Door Station or SEP02 is not communicating with the Comfort panel.
The ID address of the unit which is not communicating is reported. This
ID identifies which unit is giving the problem, according to the table
below:
717
35
3
70
6
342695
331684
SEP02
673
50
2
66
2
491651
IDDoor StationIDKeypad
1 Check the wiring to the unit concerned.
2 If Communications Failure happens each time on Security Off, the
power may have been connected to S12V. Keypad power should be
connected to 12V terminals.
Keypad Beeps continuously
If a Keypad is beeping continuously, it means that it has not received
any RS485 communications on the KA/KB lines for the last 6 seconds.
The beeps will continue until any key is pressed or if communication
resumes. The beeping does not occur if the unit can receive
communications but is not addressed by the Control panel, due to
settings in Locations 1674 and 1675.
1 Check that the KA/KB are connected to KA/KB on the Comfort panel,
double-check they are the right way round.
2 If all Keypads and Door Stations beep continuously, it means that the
problem could lie on the Comfort panel or could mean that all of the
KA-KB comms connection are crossed. Check there is voltage 13.8V on
the 12V terminal.
Cannot Sign In on Keypad
If the Keypad is not beeping continuously as described above, it
probably means that communications can be received but the ID is not
set up or voice is not connected.
1 Check that all other Keypads are not in use, for example in Security
Check which does not time out. Press F on the active Keypad to exit.
2 Check that the Keypad/Door Station ID (SW1) and Keypad/ Door
Station selection (JP5) is correctly set for each Keypad and Door
Station.
3 Next check that Location 1675 is set to the number of Keypads and
Location 1674 to the number of Door Stations. The Comfort system
must be reset after changing Locations 1674 and 1675
Comfort Installation Manual