Circuits with this On response will cause a short two-tone ‘chime’ sound
at the Keypads and speakers . This may be disabled by the user in Alert
Menu 6 in Home Control. (Siren Type 20)
85 Cancel Entry in Night Mode
Circuits with this On response will perform an immediate alarm if
activated during Night Mode and respond as normal when in Away
Mode.
86 Double Knock - Ext. Movement Detector
Circuits programmed with this On response will only cause an alarm
condition if the circuit is activated twice within the double knock time
window of 20 seconds. Refer to the full details of this response in Table
33. If another detector triggers also with this response activates after
the first detector, then the alarm will be activated. If the detector
requiring double knock is internal such as a PIR or active shock
detector, then reduce the time window to 10 seconds in the Response.
If you would rather the detector simply dials-out instead of activating
the sirens, change the zone-type to produce a perimeter or alert alarm.
86 Vibration Analyser (modified)
Intended for a circuit that has an operating sensitivity of 20 ms which is
suitable for use with non-electronic (mechanical) inertia shock
detectors. This Response 86 will require modification for use on low
cost inertia detectors. The values of 5 seconds should replace the 20
and will only cause an alarm condition if the circuit is activated twice
within the double knock time window of 5 seconds. Refer to the full
details of this response in Table 33.
93 Intelligent Setting to Night Mode
Circuits with this On response will change the ‘Away’ arming to ‘Night ‘
Mode when the zone is entered. This Response would be applied to say
a Landing PIR, and MUST be triggered as the user retires to Bed after
first selecting Away Mode, opening and closing the exit door may
defeat.
189 Stop Door Station Ringer
This Response stops the local phone ringer following the doorbell being
pressed. It may be used in a Zone Response for the front door or a PIR
‘en route’ to stop the phones from ringing while on the way to answer
the door or when the door is opened. Uses action code 26.
Soak-Test - Zone Type 17
To help evaluate a detectors stability it is sometimes necessary to put it
‘on test’. This ensures that if it activates during the time it is ‘on test’ it
can do no harm as it will not trigger any sounders, however, it will
stamp the log in the usual way and the user is informed of the circuit
failure when un-setting and setting the system. You will need to change
the zone type of the zone to be tested to ‘17 ‘. This will be active only
in Day and Away Modes. If required, you may have the zone dial-out to
report to the central station or voice phones by enabling the dial-out
numbers in the Soak test Alarm Type ‘17’ menu in Engineer Menu 2.
Comfort Installation Manual
74