Installation manual
type can be assigned to any one of these filter settings for each security
mode (Security Off, Night, and Away/Holiday). The use of Alert and
Perimeter Zones is a useful tool in preventing false alarms, but requires
careful planning and design on the part of the installer. Refer to the
table below for the flowchart which explains the sequence of zone
activation to trigger an alarm.
Alarm Type for Zone
(Intruder, Fire etc)
Instant Zone
Alert State
Intruder Alarm
Same zone activated
Idle State
PerimeterAlert
State
Other Perimeter Zones
Instant or Alert Zone
Alert Zone
Instant, Perimeter or other Alert Zone
Perimeter Zone Activated
Entry Delay
Entry Door
Entry Door
Figure 3.2 - Flowchart for Instant, Alert and Perimeter Zone Activation
Table 9 - Zone Types (Alarm Type Assignments)
Each Zone Type is assigned to 2 Alarm Types. The Normal Alarm type is
the Alarm which is triggered when the zone is activated when it is not
Inactive (i.e. it is Instant, Alert, or Perimeter). The Armed Trouble
Alarm Type is the Alarm which is triggered when the Zone is in Trouble
state, i.e. open or short circuit wiring (2 End of line resistors must be
used), AND the system is armed (Day, Night or Away mode). For
example, Zone Type 1 which is defined as Instant in Away, Night, and
Day modes, will trigger the Intruder Alarm when armed. When armed
and Zone trouble is detected, it will also cause an Intruder alarm
because of the Armed Trouble setting. Zone Trouble detected when
the system is not armed (i.e. in Security Off Mode) always causes a
Zone Trouble alarm (Alarm Type 5) The table shows the default Alarm
type settings for each Zone Type and how to change these settings
using Locations.
Comfort Installation Manual
68