Installation manual

J4
2K7 EOL resistor required
for UL installations
TamperTamper
Tamper
COM
J4
0V - TR
Remove Link to
enable panel
case- tamper
CPU Tamper
Switch - (N.C.)
0V
Tamper
Return.
European Versions
International Versions
Figure 2.12 Tamper Input connection
‘Negative Applied’ Detectors
Certain types of detector such as outside PIR’s and photocells provide
an open-collector output as a trigger rather than a relay output. This
type of signal can be connected directly into a zone terminal providing it
is a negative signal in one state and ‘floating’ in the other state. If the
signal goes negative when detecting, use a normally-open zone type
such as Type ‘8’ (normally-open switch). This is suitable for light
sensors or external non-alarming detectors which may be used as
monitors to drive Responses for lighting and CCTV applications.
The negative signal should be applied to non-eol zone where the trigger
wire connects just to one side of the zone, provided the detector has a
12v supply derived from the panel acting as a reference.
If tamper protection is required on the zone, three wires will be
required and the zone jumper should be removed from the header. A
single 2K7 resistor should be fitted in series with two of the wires at the
detector. The detector’s negative trigger should then connect to the
side of the resistor and wire which returns to the zone terminal and
Comfort Installation Manual
42