Installation manual

The 2 EOL resistors should be connected at the contact and not at the
control panel. With 2 EOL resistors connected in this way, the system is
able to distinguish open and closed contacts from open circuit and short
circuit wiring providing full supervision of the zone contacts and cables.
Any short or open circuit fault will trigger a Zone Trouble Alarm which
can be reported to the programmed phone numbers. Where double
end-of-line resistors are used, the following circuit resistances should
be measured and verified on the zone wiring PRIOR to their connection
into the zone terminals. Use them as a guide when commissioning a
system or tracing a fault.
Also check that there is no short circuit between the 12V auxiliary
supplies and zone circuit wiring and the power cables connected to the
auxiliary supplies do not contain any shorts between 0v and 12V.
zeroShorted / Fault
Open circuit (infinity)
Tamper / Fa
ult
7 K 4Open / Active
2 K 7Closed /Healthy
Zone Resistance (Ohms)
Status
4-wire Smoke Detectors (End Of Line)
Smoke Detectors are usually connected as Normally Closed (N.C). The
corresponding Header JZ1 to JZ8 should have a shunt (shorting link)
inserted into the position away from the terminals. Smoke and Heat
Detector zones are programmed as Fire Zone Type 23. A Pulsed On/Off
siren pattern indicating Fire Evacuation is produced when this zone type
is activated (by default). If the zone wiring is cut or open-circuit or
shorted, a Zone Trouble alarm is generated for fire zones using EOL
resistors.
Connection of Multiple Shock Detectors to a zone
The system has the unique ability to announce the type of the
activated zone during Security Check (during arming) , alarm history,
alarm tracking, and event log. So if more than one detector is
connected to a zone input, it should ideally be of the same type and in
the same location, for example, magnetic contacts for several windows
in the same room. The following diagram shows shock detectors on the
same zone. Some ‘active’ vibration detectors such as Optex can latch
their LED on following an alarm for identification. To make the most of
this feature, supply the detectors via a normally closed relay connected
to an output. Use the arming response (location 1850) to pulse the
output using a response to reset the detectors during arming by
interrupting their the supply, this may announce their zone briefly
during arming.
Comfort Installation Manual
40