Installation manual

(( If your system is connected to a PABX extension (not
permitted for UL installations), do not include the PABX access
digit as part of the phone number. You should use the PABX
settings instead (7,2,1). Always connect the system to the
default extension, which will have access to an outside line
when there is a power failure. The system will not dial a PABX
outside line digit if there is a power failure.
(( The system should not be programmed to dial to the police
station unless the number has been specifically assigned by
the police station to provide such a service.
Entry/Exit Time (4,2)
Press 0 for Entry Time,
1 for Exit time,
2 for Entry Warning Time
3 for Night Exit Time
Entry Time (4,2,0)
20 seconds, enter new number and # key
Enter new entry time in seconds and #, or just # to leave the value
unchanged.
The Entry time is the time allowed after entering the designated Entry
Door when the system is armed to allow the user to sign-in. If the entry
time expires without a valid sign-in, a local Warning Alarm (Alarm Type
6) will be generated for the duration of the Entry Warning Time This
produces a warning alarm on the Speaker only. If the Entry Warning
Time is set to zero, the Entry Warning Alarm is bypassed, and the
system will go into a full Intruder Alarm when the Entry Time expires.
(( For BS4737 installations, the combined Entry Time plus Entry
Warning Time should not exceed 45 seconds.
Exit Time (4,2,1)
20 seconds, enter new number and # key
Enter new exit time in seconds and #, or just # to leave the value
unchanged.
The Exit time is the time in seconds allowed after arming the system
locally for the user to exit through the designated Entry Door when the
system says "Please Exit" after passing the Security Check. If the Exit
Time expires without closing of the Entry Door, the system will not be
armed, it will remain in Security Off Mode. An Arm Failure Alarm
(Alarm Type 4) is generated. As with all alarm types, this may be
programmed to dialout and activate a response if needed. The default
Arm Failure alarm generates a series of beeps on the speaker and does
not do a dial out. If during arming the Security Check finds some
Comfort Installation Manual