Installation manual
pressing 1 for next event, 2 for previous event, 0 for 1st event, 9 for
last event, 3 for Next Day, 4 for Previous Day. See Engineer Menu 5,1
for a full description of the events which are recorded.
False Alarm on Disarming
This may be caused by connecting PIRs or Keypads to the S12V output
instead of the 12V terminals. S12V and 12V share the same terminal
block. S12V is meant for detectors which need to be reset on
disarming, and is switched off for 5 seconds when the system is
disarmed. PIRs programmed as 24 hour zones which have their supply
connected to S12V will activate when disarmed. Also Keypads which are
powered from S12V will report ”Communication Failure”.
There is now an Arming response (Location 1850) which allows shock
detectors to be reset during the exiting procedure instead of at the
point that the system is disarmed (which resets the detector before the
culprit has been identified). You can feed such detectors via a relay
which is normally closed and pulse the output feeding the relay using a
pulsed output responses (eg. 130,20,8 = pulse OP8 for 1 second),via
the Arming Response Location 1850.
Zone Troubles
Go into Security Check (Eng Menu 8,2) or Function 3,2 on Keypad. The
names of the zones activated are announced. If 2 End-of-line resistors
are used on zones, open-circuit and short-circuit wiring are announced
as “Zone (N) Trouble” instead of by their zone names. If zones are
open or ‘normally open’ on entering Security check, they are announced
once upon entry into the Walktest Menu at the beginning, to hear their
status again, press #2 and re-enter the menu.
How to recover lost User Codes
If users other that User 1 (Master code) forget their codes, the User
program Menu can delete them and Add the code again (in Program
menu 5,2). If the Master Code (for User 1) is lost, the Engineer can get
into program Menu by Pressing F+0, then Engineer menu, and then 9
for Program menu. Then press 5 for User Codes and 2 to erase User 1
and add the user again.
Is the Siren Duration restarted during Alarm by new zone activations?
The siren duration starts when a zone is triggered to cause an alarm. If
another zone is triggered while the siren is still on, the siren continues
but the timer is not restarted if the same siren type is activated. The
siren will time out according to the programmed duration after the
original activation. However, if a different siren type is activated, e.g. a
Fire Alarm Siren after an Intruder alarm siren, then the new siren
duration will take effect.
Comfort Installation Manual
100