Technical information
IM-P405-39 AB Issue 4
22
6. Commissioning
6.1 General information
All commissioning for the product is carried out using the front panel. The front panel consists
of a graphics display and a 5-button keypad - See Figure 10 and Section 2.
Warning: On entering the commissioning mode the product will cease normal control.
The control relay will shut the valve. For safety, the alarm relay will continue to operate
as normal. To regain normal control, return to the run menu.
Warning: If during commissioning, the buttons are not pressed for over 5 minutes, the
controller will revert to run mode and an error will be displayed. If the commissioning
was incomplete the controller may not provide the correct control.
The programmed settings are held in non-volatile memory (Flash) and are written to after
changing a parameter and pressing the
OK
button. For quick set-up see Section 6.2.
An internal battery is used to keep the clock calendar running when the mains supply
is switched off. To connect the battery, set both of the battery back-up switches (see
Section 5.3), to the on / down position.
Note: If the product has been powered down with the battery switched off, the display will
show a spurious time and date on power up. To correct this, switch on the battery and
enter the correct time and date.
Fig. 10 Front panel display
Enter sub-menus and
shift right to the next digit
when the parameter or
digit is flashing.
Scroll up
menus / sub-menus to
Increase digits
Enters parameters when the
parameter or digit is flashing.
Hold down for 5 seconds to
enter commissioning mode.
Exit sub-menus and shift left
to the next digit when the
parameter or digit is flashing
Graphic display
BT1050
OK
Scroll down
menus / sub-menus to
Decrease digits