User Manual
Water Manometer
When using a water manometer to measure the mani
fold pressure, proceed as follows to adjust the gas in
put:
1.  Turn  off  gas  to  unit.  Connect  manometer  to  1/8- 
inch pressure tap at outlet of gas valve.
2.  Turn on  gas to unit. With burners fired and both 
first  and  second  stage  gas  valves  open,  adjust  the 
pressure  regulator  to  obtain  the  correct  manifold 
pressure  as  shown  in  Table  II.  Check  with  local  gas 
utility for Btu value and specific gravity of gas in the 
area.
TABLE II
BTU
Specific Gravity
Value 0.59 0.61
0.63 0.65
0.67
900
3.8 3.9
4.0
4.1
4.2'
950
3.3
3.4
3.5
3.6 3.7
1000 3.0
3.1 3.2 3.3
3.4
1025 2.8 2.9 3.0
3.1 3.2
1050
2.7 2.8 2.9
3.0 3.1
1100
2.4
2.5
.L.C 2.7
2.8
Example; Heating  value  of gas in the  area  is 1030 
Btu; Specific gravity is 0.62.
(a)  From Table II the manifold pressure required for 
450,000 Btuh is 3.0 inches wc.
(b)  Set manifold pressure to 3.0 inches water column 
by adjusting gas pressure regulating screw.
If  the  required  manifold  pressure  exceeds  3.3  inches 
w.c. or is less than 2.7 inches w.c., the orifices should 
be sized according to unit requirements.
CAUTION: Do not redrill orifices under any circum
stances.
Air Shutter Adjustment
To  adjust the  primary  air to  each burner,  partially 
close the air  shutter  until there is  a slight yellow  tip 
on the top of the flame, then open the air shutter until 
the yellow tip just disappears. This should be done af
ter the burners have been operating at full input for 5 
or 10 minutes (approximately).
Temperature Rise
Models 450-379H, 180R-, and 240R-379 are designed 
for operation within a temperature rise range of 20 °F 
to  75°F  against  an  external  static  pressure  up  to  1.0 
inch water column.
NOTE:  Temperature  rise  is the  difference between 
the temperature of the air in the return air duct and 
the temperature of the air in the discharge duct near 
the heating section.
SECTION VIII. MAINTENANCE
Lubrication: Refer to the rating plate for the blower 
motor lubrication requirements.
Cleaning the Heating Unit
1. Be sure that main line disconnect switch is in OFF 
position.
TAG  SWITCH  WITH  SUITABLE  WARNING 
LABEL.
2. Remove front access panel.
3. Turn off manual gas valve and pilot valve.
4. Disconnect pilot and escapement tubing.
5. Remove burners.
6. Remove flue baffle retainer and the flue baffles.
7. Clean flue passages with suitable brush.
8. Reassemble furnace by reversing above procedure, 
making sure all seals are reinstalled properly.
9. Check belt  conditions and for  proper  belt tension 
(1/2 inch deflection).
Filter
Filters  in  Models  240R-  and  450-379H  are  of  the 
permanent type and should be inspected and cleaned 
at regular intervals. Filters used in Model 180R-379H 
are of the disposable type and should be inspected 
and replaced with filters of the same type and size. In
spections should be made on a regular basis; the time 
interval  between  inspection  will  depend  on  the  type 
of application.
-5-
39379D35






