Owner's manual
Installation Instructions
379H
Size 450 
180R & 240R 
Series D
OUTDOOR HEATING AND COOLING UNIT / bPliant
I
39379D35 
1/3/72
The Bryant Model 4dO-379H is a heating unit designed 
for  outdoor  installation;  either  rooftop  or  at ground 
level.  It  is  available  with  either  of two  factory-in
stalled direct expansion coils (Model 180R- or 240R- 
379) or  with no  expansion coil  as Model  450-379H. 
Model  180R  units  are  equipped  for  use  with  R22 
refrigerant  and  provide  180,000-Btuh  cooling  when 
connected  with  a  Bryant  Model  180-566  Condensing 
Unit.  Model  240R units  are  equipped  for use  with 
R500  refrigerant  and  provide  240,000-Btuh  cooling 
when  connected  with  a  Bryant  Model  240-566  Con
densing Unit. All tluree models have a heating input of
450.000  Btuh  (approximately)  for  both  natural  and 
propane  gas.  They  are  equipped  with  a  two-stage 
firing arrangement for operation at a reduced input of
225.000 Btuh.
.! ,Fi L
DO NOT!
IREMOVE
Important-Read Before Installing
Be  sure  the  available  gas  supply  is  the  same  as  that 
shown  on  the  American  Gas  Association  (A.G.A.) 
rating plate. Check the electrical  supply to be sure 
that voltage, frequency, and phase correspond to that 
specified on the unit rating plate.
Check all national, state, and local building codes af
fecting the installation of this unit. Check all local or
dinances that could affect the installation of this type 
equipment.
WARNING: All access panels must be in place at all 
times when unit is in operation.
GENERAL
The design  of the unit  is certified  by the  American 
Gas Association (A.G.A.) for use with iiatural or pro
pane  gas  with  the  appropriate  controls  and  orifices. 
The  units are  designed specifically  for outdoor  in
stallation, either at rooftop or ground level.
Installation of the unit consists of the following:
I.  Locating the Unit
II.  Gas Piping
III.  Duct Connection
IV. Venting
V.  Coil Connection (Models 180R- and 
240R-379H)
VI.  Electrical Connections
VII.  Start-up and Adjustments
VIII.  Maintenance
Figure 1
SECTION I. LOCATING THE UNIT
Extreme caution should be observed to prevent dam
age when moving the unit. Maintain the unit in an up
right position at all times during rigging and moving 
operations.  To  facilitate  lifting  and moving  opera
tions,  place  the  unit  in  an  adequate  rope  or  ca
ble sling.
CAUTION: Protect the top and sides of the unit from 
possible damage from rigging sling.
Rooftop Installation
Level the unit on a base situated a minimum of 6 in
ches above the roof to insure proper drainage. Consult 
local and state building codes for installation require
ments. Be  assured the  roof construction  will support 
the weight of the equipment.
Ground Level Installation
The unit should be placed on a level concrete slab (4- 
inch  minimum  thickness);  level  the  unit  on  the  slab 
with 1-inch clearance to insure proper drainage.
Combustible Clearances
Minimum clearances are: 6 inches from rear or duct 
side,  24  inches  on  all  other  sides,  and  0  inch  on  the 
bottom. These clearances permit the use of combus
tible materials for supports. The top of the unit must 
be kept clear at all times.