Instruction manual
27
Option 11 — Deadband Setting Between Heat & Cool
This option is not available on Heat Only and Cool Only systems. The selection
allows the installer to choose how much differential exists between the heating
and cooling setpoints. Allowable selections are 1 --6.
Default is 2 .
Option 12 — Smart Recovery
Smart Recovery OF (off) means setpoints change precisely at setback recovery
time. Thirty, 60, or 90 selects the number of minutes recovery starts before
programmed recovery time. Recovery takes place smoothly during the selected
recovery time, ending at the recovery time and temperature which is
programmed. Not available with non-- programmable thermostats or when
thermostat is configured as non-- programmable.
Default is 90.
Option 13 — Room Air Temperature Offset Adjust
The number of _F to be added to the displayed temperature to calibrate or
deliberately miscalibrate the measured room temperature ( --5 to +5_F).
Default is 0 .
Option 14 — Humidity Display Offset Adjust
The percentage to be added to the displayed humidity to calibrate or deliberately
miscalibrate the measured room humidity (--9% to +9% RH).
Default is 0 .
Option 15 — Enable Auto Mode
This selection is not available if the thermostat is configured as Heat Only or
Cool Only in Option 1. This allows the homeowner to select auto changeover
mode in addition to heat and cool. This allows the thermostat to automatically