Instruction manual
80
thermostat, momentarily turn off the FAN switch or push
button on the room thermostat for 1--3 seconds after the
blower motor BLWM is operating. The furnace control
CPU will shift the continuous--blower airflow from the
factory setting to the next highest CF selection airflow as
shown in Fig. 55. Momentarily turning off the FAN switch
again at the thermostat will shift the continuous--blower
airflow up one more increment. If you repeat this procedure
enough you will eventually shift the continuous--blower
airflow to the lowest CF selection as shown in Fig. 55. The
selection can be changed as many times as desired and is
stored in the memory to be automatically used following a
power interruption.
NOTE: If the blower--off delay is set to the maximum, the
adjustable continuous--fan feature is locked (i.e., fan speed cannot
be changed from its current setting).
6. Heat pump
See Fig. 35 and 36 for thermostat connections.
When installed with a heat pump, the furnace control auto-
matically changes the timing sequence to avoid long blower
off times during demand defrost cycles. Whenever W/W1 is
energized along with Y1 or Y/Y2, the furnace control CPU
will transition to or bring on the blower motor BLWM at
cooling airflow, low--heat airflow, or the mid--range airflow,
whichever is lowest. The blower motor BLWM will remain
on until the main burners ignite then shut OFF and remain
OFF for 25 seconds before coming back on at heating
airflow. When the W/W1 input signal disappears, the
furnace control begins a normal inducer post--purge period
while changing the blower airflow. If Y/Y2 input is still
energized the furnace control CPU will transition the blower
motor BLWM airflow to cooling airflow. If Y/Y2 input
signal disappears and the Y1 input is still energized the
furnace control CPU will transition the blower motor
BLWM to low--cooling airflow. If both the Y1 and Y/Y2
signals disappear at the same time, the blower motor
BLWM will remain on at low--heat airflow for the selected
blower--OFF delay period. At the end of the blower-- OFF
delay, the blower motor BLWM will shut OFF unless G is
still energized, in which case the blower motor BLWM will
operate at continuous blower airflow.
7. Component self--test
The furnace features a component test system to help
diagnose a system problem in the case of a component
failure. To initiate the component test procedure, ensure that
there are no thermostat inputs to the control and all time
delays have expired. Turn on setup switch SW1--6. (See
Fig. 35.) Refer to Page 70 for instructions.
986TA