Instruction manual
81
The furnace will start up in either intermediate-, or maximum-heat.
The furnace will operate in minimum-heat after starting and
operating for 1 minute at intermediate-heat before transitioning to
minimum-heat.
The wall thermostat ”calls for heat”, closing the R to W1 circuit for
minimum-heat or closing the R to W1-and-W2 circuits for
maximum-heat. The furn ace con trol perfo rm s a self-check , and
veri fies th e low, medium and high pressure switch contacts LPS,
MPS and HPS are open, then de-energizes the PSR relay to close
th e NC contact.
The start up and shut down functions and delays described above
apply to the 2-stage minimum/maximum heating mode as well,
except for switching from maximum- to minimum-heat.
1. Switching from Maximum- to Minimum-Heat —Ifthe
thermostat R to W2 circuit opens, and the R to W1 circuit
remains closed, the furnace control CPU will gradually de-
crease the inducer motor speed to the required intermedi-
ate-heat RPM. When the inducer motor IDM reduces pres-
sure sufficiently, the high pressure switch HPS will open
and the gas rate will be changed to intermediate-heat. The
gas valve solenoid GV (pin 5) will remain energized as long
as the low pressure switch LPS remains closed. When the
inducer motor speed gets within 15% of the required inter-
mediate-heat RPM the furnace control CPU will start a 5
second blower airflow change delay. After the 5 second
blower airflow change delay is completed the blower air-
flow will transition to minimum-heat airflow. At this point
the furnace control CPU will energize the PSR relay to open
the NC contact and slowly decrease the inducer motor
speed to th e required min im u m -h eat R P M . Wh en the
PSR relay is energized and the NC contact opens the fur-
nace control CPU will reduce the gas rate to minimum-heat
RPM.
Two-Stage Thermostat and Two-Stage Intermediate/
Maximum Heating
See Fig. 34 and 35 for thermostat connections
NOTE: In this mode the intermediate-heat only switch SW4-2
must be ON to select the intermediate-heat only operation mode in
response to closing the thermostat R to W1 circuit. Closing the
thermostat R to W1-and-W2 circuits always causes
maximum-heat operation, regardless of the setting of the
intermediate-heat only switch.
The wall thermostat ”calls for heat”, closing the R to W1 circuit for
interm ed iate-h eat o r clo sin g the R to W1 -and -W 2 circuits fo r
maximum-heat. The furnace control performs a self-check, and
verifies the low, medium and high pressure switch contacts LPS,
MPS and HPS are open , then de-energizes the PSR relay to close
the NC contact.
The start up and shut down functions and delays described above
apply to the 2-stage intermediate/maximum heating mode as well,
except for switching from maximum- to intermediate-heat.
1. Sw itch ing from Ma x im u m - to Interm ed ia te-H ea t — If
th e thermostat R to W2 circuit opens, and the R to W1 cir-
cuit remains closed, the furnace control CPU will gradually
decrease the in du cer mo tor speed to th e req uired interme-
diate-heat RPM. When the inducer motor IDM reduces
pressure sufficiently, the high pressure switch HPS will
open and the gas rate will be changed to intermediate-heat.
When the inducer motor speed gets within 15% of the re-
quired intermediate-heat RPM the furnace control CPU will
start a 5 second blower airflow change delay. Af ter t he 5
second blower airflow change delay is completed the
blower airflow will transition to intermediate-heat airflow.
Cooling Mode
The thermostat “calls for cooling.”
1. Single-Speed Cooling
See Fig. 34 and 35 for thermostat connections.
The thermostat closes the R to G-and-Y circuits. The R to Y circuit
starts the outdoor unit, and the R to G-and-Y/Y2 circuits start the
furnace blower motor BLWM on cooling airflow. Cooling airflow
isbasedontheA/CselectionshowninFig.54.
The electronic air cleaner terminal EAC-1 is energized with 115
vac when the blower motor BLWM is operating. When the
thermostat is satisfied, the R to G-and-Y circuits are opened. The
outdoor unit will stop, and the furnace blower motor BLWM will
continue operating at cooling airflow for an additional 90 seconds.
Jumper Y/Y2 to DHUM to reduce the cooling off-delay to 5
seconds. (See Fig. 34.)
2. Single-Stage Thermostat and Two-Speed Cooling (Ad-
aptive Mode)
See Fig. 34 and 35 for thermostat connections.
This furnace can operate a two-speed cooling unit with a
single-stage thermostat because the furnace control CPU includes a
programmed adaptive sequence of controlled o p e ration, wh ich
selects low-cooling or high-cooling operation. This selection is
based upon the stored history of the length of previous cooling
period of the single-stage thermostat.
NOTE: The air conditioning relay disable jumper ACRDJ must be
connected to enable the adaptive cooling mode in response to a call
for cooling. (See Fig. 34.) When in place the furnace control CPU
can turn on the air conditioning relay ACR to energize the Y/Y2
terminal and switch the outdoor unit to high-cooling.
The furnace control CPU can start up the cooling unit in either
low- or high-cooling. If starting up in low-cooling, the furnace
control CPU determines the low-cooling on-time (from 0 to 20
minutes) which is permitted before switching to high-cooling.
If the power is interrupted, the stored history is erased and the
furnace control CPU will select low-cooling for up to 20 minutes
and then energize the air conditioning relay ACR to energize the
Y/Y2 terminal and switch the outdoor unit to high-cooling, as long
as the thermostat continues to call for cooling. Subsequent
selection is based on stored history of the thermostat cycle times.
The wall thermostat “calls for cooling”, closing the R to G and- Y
circuits. The R to Y1 circuit starts the outdoor unit on low-cooling
speed, and the R to G-and-Y1 circuits starts the furnace blower
motor BLWM at low-cooling airflow which is the true on-board
CFselectionasshowninFig.54.
If the furnace control CPU switches from low-cooling to high
cooling, the furnace control CPU will energize the air conditioning
relay ACR. When the air conditioning relay ACR is energized the
R to Y1-and-Y2 circuits switch the outdoor unit to high-cooling
speed, and the R to G-and-Y1- and-Y/Y2 circuits transition the
furnace blower motor BLWM to high-cooling airflow.
High-cooling airflow is based on the A/C selection shown in Fig.
54.
NOTE: When transitioning from low-cooling to high-cooling the
outdoor unit compressor will shut down for 1 minute while the
furnace blower motor BLWM transitions to run at high-cooling
airflow.
The electronic air cleaner terminal EAC-1 is energized with 115
vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G-and-Y circuit are
opened. The outdoor unit stops, and the furnace blower BLWM
and electronic air cleaner terminal EAC-1 will remain energized for
an additional 90 seconds. Jumper Y1 to DHUM to reduce the
cooling off-delay to 5 seconds. (See Fig. 34.)
987MA