GUIDE SPECIFICATIONS 538S CONDENSING UNITS (cont)
2. Safeties:
a. High condensing temperature protection (when
matched with 619E fan coils).
b. System diagnostics (when used with 619E fan
coils).
c. Compressor motor current and temperature over-
load protection.
d. High pressure relief.
e. Condenser fan failure protection.
H. Electrical Requirements:
1. Unit shall operate on single-phase, 60 cycle power at
208/230 v as specified on contract drawings.
2. Unit electrical power shall be a single point
connection.
3. Unit control voltage to the indoor fan coil shall be 24 v.
4. All power and control wiring shall be installed per NEC
and all local building codes.
5. Unit shall have low-voltage terminal block connections.
I. Special Features (Field Installed):
Certain features are not applicable when the features
designated by * are specified. For assistance in amending
the specifications, contact your local representative.
* 1. Winter Start Control:
Field-installed winter start control shall permit start-up
for cooling operation under low-load conditions and at
low-ambient temperatures by bypassing the low-
pressure switch for a 3-minute delay period.
NOTE: Winter start control shall be required when unit
is intended to operate in cooling at outdoor ambient
temperature below 40 F.
2. Crankcase Heater:
Field-installed crankcase heater shall be a clamp-on
compressor oil sump heater. Heater shall be used in
all applications where operation in cooling below 40 F
outdoor ambient temperature is anticipated.